LAARS Heating Systems

SECTION 1
General Information

1A. HW Series, H Series, HP Series

The H Series boiler is a low pressure, hot water

boiler that is available in two (2) design

configurations. The HW series provides domestic hot

water as well as hydronic space heating. It includes an

insulated storage tank through which boiler water is

circulated. A heat exchanger within the tank transfers

heat from the boiler to the domestic hot water. The H

and HP series boilers are designed to provide hot

water for space heating, and can be plumbed to an

indirect water heater to supply domestic hot water.

By replacing the air and the gas orifices, the

basic H Series boiler has the flexibility to operate on

either natural or LP gas and may be fired at 60,000,

100,000 or 130,000 BTU/HR input. The H Series can

be direct vented by utilizing an optional concentric

vent system that will provide outside air for

combustion. H(W)(P)-60,100 & 130 appliances may

also be vented with 3" or 4" diameter stainless steel

horizontal / vertical venting as described on page 6.

The maximum length shall not exceed 50 equivalent

feet of 3" diameter or 100 equivalent feet of 4"

diameter. H(W)(P)-M2-130 appliances may also be

connected to a lined internal chimney.

The H Series features a forced draft, pre-mixed

combustion system. All air for combustion is supplied

with the gas to the burner (flameholder). Both the

intake air and the gas are metered through separate

orifices before entering the combustion air blower.

The blower forces the air/fuel mixture through the

flameholder and into the combustion chamber. The

mixture is ignited from the hot surface igniter and

burns. Hot gases are forced out between the passes of

the heat exchanger into the flue collector. Flue gases

are discharged into the outside atmosphere through the

vent terminal, a chimney, horizontal or vertical

alternate vent.

Model H(W)-M2-60 & H(W)-M2-100 UNITS

MUST NOT BE CHIMNEY CONNECTED.

Installations with water containing 10 grains of

hardness or higher, must be installed with appropriate

water treatment.

1B. To the Installer: Before You Begin

The H Series is uniquely different from any

heating boiler you have installed in the past. It is

important for you to take a few minutes to review the

contents of the Installation and Operating section of

this manual before you begin installation. This will

avoid making mistakes and causing confusion when

installing and operating the unit.

1.

Gas Burner*

2.

Sealed Combustion* w/ P/N 2400-236 or

2400-238

3.

Outside Vent Wall*

4.

Outside Air For Combustion*

5.

Copper Coil Heat Exchanger*

6.

Thermostatic Union (H-M2)

7.

Domestic Hot Water Coil (HW(D)-M2)*

8.

Heating System Water Outlet

9.

Heating System Water Return

10. Gas Supply

(*see Figure 1)