2E. Installing Stainless Steel

Horizontal / Vertical Venting
(non concentric)

Stainless Steel Special Gas Vent listed to U.L.

Standard 1738 and U.L.C. Standard 636 may be used

to vent all H Series H(W)(P) and DH(P) models. Vent

pipe and fittings are manufactured to these Standards

by Heat-Fab, Inc. under the trade name of Saf-T

Vent® and by Z-Flex™ under the trade name of

Z-Vent. Follow the Special Gas Vent manufacturers’

instructions regarding design, location and assembly

of the vent system.

The H Series appliance may be vented with any

number of elbows or fittings provided that the

maximum equivalent feet of venting is not exceeded.

90° elbows in the vent system shall be considered to

be 10 equivalent feet. When vented with Special Gas

Vent, the H Series must not be common vented with

any other appliance.

2F. Connecting Special Gas Vent

to H Series

Teledyne part number 2400-372 (Figure 6) is

used to secure the Special Gas Vent to the flue outlet

of the H Series*. Heat-Fab pipe or fittings (part

numbers 2400-350 or 2400-352) or the male end of

Z-Vent pipe (Z-Vent # 02 SVEPXX030) may be

installed over the flue outlet of the H Series.

*If a duct is used around the Special Gas Vent to

bring in combustion air from another location, the

connection of that duct to the appliance must be

secured with sheetmetal screws.

Each joint between the appliance and the last

joint before the location where the Special Gas vent

exits the duct must also be secured with sheetmetal

screws.

In this application, part number 2400-372 is not

used at the boiler flue collar. It is used, and must be

used, to secure the Special Gas Vent at the point

where the Special Gas Vent exits the duct.

The combustion air supply should be protected

from debris entering the duct. This may be done with a

H Series Vent Terminal, part number 2400-277, as

shown in Figure 7 or with a large mesh screen.

Follow the Special Gas Vent manufacturer’s

instructions for cleaning and sealing all parts before

assembling.

2G. Appliance Joint Procedure

Part #2400-350 (See Figure 8)

Apply 1/4" bead of silicone sealer (GE108 or

Novagard 400) to the 3 inch (3") flue outlet of the H

Series approximately one inch (1") from the end.

Slide flue adapter over the H Series flue outlet

(flared up end) and push down to stop (do not force

adapter beyond stop).

Apply another bead of silicone around this joint

and smooth out.

Apply 1/4" bead of silicone to the straight end of

the 2400-350 pipe approximately 1/4" from the end.

Slide the pipe into the adapter until it bottoms in

the adapter.

Apply another bead of silicone around this joint

and smooth out.

2H. Appliance Joint Procedure

Part #2400-352 or Z-Vent

#02SVEPXX030 (see Figure 8)
Apply 1/4" bead of Silicone sealer (GE 108 or

Novagard 400) to the 3 inch (3") flue outlet of the H

Series approximately one inch (1") from the end.

Slide pipe over the H Series flue outlet and push

down to stop (do not force pipe beyond stop).

Apply another bead of silicone around this joint

and smooth out.

2I. Securing Special Gas Vent

Attach part number 2400-372 to 5" collar on

appliance or end of five inch (5") combustion air duct

and tighten large clamp.

Form tabs on part number 2400-372 onto Special

Gas Vent pipe and secure tabs with the 3" clamp.

After the clamp has been tightened, fold the end

of the tabs down over the clamp.

DO NOT use screws in any portion of the 3"

Special Gas Vent.

For vertical venting see instructions in the

Vertical Vent Kit pertaining to use of raincaps and

condensate drip tee's.