Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 27

Advertising
background image

H Series

Page 27

possible to check for cross contamination in another

way. Loosen the top clamp on the air duct coupling

and remove the gas balance line from the “Tee

fitting”. Lift up the air induction elbow and twist it to

the side so that air from the space around the boiler

can be drawn into the air duct coupling (do not disturb

the air orifice in the coupling). Cover the air induction

elbow with your hand or plug it with a rag and restart

the boiler. If no short cycling occurs there is a leak in

the 3" flue pipe which must be corrected. Do not leave

the boiler operating in this manner. Reassemble the air

duct after removing plug (rag) and connect the balance

line and stack switch tubes. Disassemble flue and fix

leak.

12G. Lock Outs

Integrated Boiler Control Lock Outs

Possible Causes

a.

Cross Contamination

b.

Moisture in Combustion Chamber

c.

Gas Valve Malfunction

d.

Poor combustion

e.

Boiler control malfunction

f.

Control contact failure
1). Stack Switch
2). Operating Control

g.

Failure of air source

h.

Igniter failure
If cross contamination is suspected see “Cross

Contamination” and check for it. One percent CO2 in

the air duct can cause nuisance lockouts.

Moisture in the combustion chamber will also

cause lock outs by weakening the flame signal to the

boiler control. It should be suspected if the boiler

temperature does not rise above 160°F during long

periods of operation. This condition can be caused by

a defective thermostat in the thermostatic union of

H(P)-M2-series boilers (or the omission of the

thermostatic union at installation) or an improperly

wired system circulator on HW-M2-series boilers. On

sidewall vented units moisture can get into the

combustion chamber from a flue pipe that is pitched

incorrectly (back toward the boiler without a

condensate trap). Quick Vented systems should

always pitch down from the boiler.

A defective gas valve (one that doesn’t always

open properly) can cause a nuisance lockout however

occurrences of this are rare.

A more common cause of nuisance lockouts is

poor combustion. If there is an odor in the flue gases,

this should be suspected. Check CO2 or O2 to

determine if combustion is within limits. Poor

combustion causes a weak flame signal to the burner

control and lock outs may result.

If combustion is within limits and none of the

causes mentioned above seems to be the cause of the

lockout it is possible that the boiler control may be

defective.

SECTION 13.
Sequence of Operation

On a call for heat from the room thermostat on

H(W)-M2 series boilers (or the low limit on the HW-

M2 series), the pump operates and the boiler control is

energized through the operating control, pressure

switch and the safety limit. It checks to ensure that the

stack switch contacts are open and then energizes the

blower. The blower starts and the air pressure

increases until the stack switch contacts close and the

red “PURGE” light lights. The pump and blower

continue to run and for 15 seconds the red “PURGE“

light stays on. Following that the red “PURGE“ light

goes out, the red “igniter” light lights and the igniter

heats for 20 seconds. At the end of the 20 seconds the

red "VALVE\FLAME" light is lit and the gas valve

is energized. For 2 seconds the valve and igniter are

energized and burner will ignite. Following this the

igniter is deenergized and the red “IGNITER” light

goes out and the pump and blower continue to run and

the burner operates under the supervision of the boiler

control. If for any reason the full sequence is

completed and the burner doesn’t ignite, the sequence

will be repeated after a blower “on “ time of 45

seconds (30 seconds post purge and 15 seconds

prepurge for the next cycle). During this part of the

sequence the igniter remains on for 30 seconds and the

balance of the sequence is unchanged. If no ignition

occurs again a third cycle will follow with the same

sequence as the second. After the third “trial for

ignition “ if the burner does not ignite the system will

“lock out” and reset can only be accomplished by

momentarily switching the power off. At the end of a

heating cycle (either space heating or domestic water

heating) after the gas valve is deenergized the blower

will continue to run for a 30 second post purge.

If normal burner operation during a heating cycle

is interrupted by any of the limit controls the unit

pump will continue to run and the blower will

continue to operate for a 30 second post purge.

TROUBLE SHOOTING (DETAILED FLOW

CHARTS ON PAGES 28-34).

If the burner “locks out” for any reason the cause

will be indicated by one of the following lights.

CODE
GREEN "POWER"
No light - no power or

Light on - see trouble shooting section.

OUT OF

PRODUCTION

Advertising