LAARS Heating Systems

9C-2. Operating Control H-M2
Burner will run until operating control cut-out

temperature (185°F) is reached.

When Operating Control cut-out temperature is

reached, burner will go off and boiler pump will

continue to run and blower will post purge for 30

seconds.

When temperature reaches Operating Control

cut-in temperature (160°F), burner will start and

continue to run until a call for heat is satisfied or

Operating Control cut-out temperature is reached

again.

9C-3. Safety Limit Operation H(W)-M2
If boiler water temperature exceeds operating

control cut-out temperature for any reason, the safety

limit will interrupt power to the gas valve at

approximately 215°F, the blower will post purge for

30 seconds and the unit will shut down. The safety

limit will reset at 195°F.

Note: temperature of limit operations are all

approximate; allow for gauge and tolerance variations.

9C-4. Stack Switch Operation H(W)-M2
If, for any reason, the combustion air blower

fails to provide adequate air flow, or if the flue is

blocked so as to prevent sufficient air flow for proper

combustion, the contacts of the stack switch will open

and the unit will shut down. After 5 minutes, purge

light will flash.

Close all covers. Reset room thermostats and

place these instructions in a place convenient to the

unit.

Please be sure that the warranty card is mailed to

by either you or the property owner.

9D. Common Vent Test

Required only if H Series is not being chimney

connected. At the time of removal of an existing

boiler, the following steps shall be followed with each

appliance remaining connected to the common venting

system placed in operation, while the other appliances

remaining connected to the common venting system

are not in operation.

Seal any unused opening in the common venting

system.

Visually inspect the venting system for proper

size and horizontal pitch and determine there is no

blockage or restriction, leakage, corrosion and other

deficiencies which could cause an unsafe condition.

Insofar as is practical, close all building doors

and windows and all doors between the space in which

the appliances remaining connected to the common

venting system are located and other spaces of the

building. Turn on clothes dryers and any appliance not

connected to the common venting system. Turn on any

exhaust fans, such as range hoods and bathroom

exhausts, so they will operate at maximum speed. Do

not operate a summer exhaust fan. Close fireplace

dampers.

Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat so

appliance will operate continuously.

Test for spillage at the draft hood relief opening

after 5 minutes of main burner operation. Use the

flame of a match or candle, or smoke from a cigarette,

cigar or pipe.

After it has been determined that each appliance

remaining connected to the common venting system

properly vents, when tested as outlined above, return

doors, windows, exhaust fans, fireplace dampers and

any other gas burning appliance to their previous

conditions of use.

Any improper operation of the common venting

system should be corrected so the installation

conforms with the 1). National Fuel Gas Code,

ANSI Z223.1 latest edition, or 2). Can / CGA - B149

When re-sizing any portion of the common

venting system, the common venting system should be

re-sized to approach the minimum size as determined

using the appropriate tables in Part 11 in the National

Fuel Gas Code, ANSI Z223.1-latest edition.

9E. Lighting and Shutdown Instructions

9E-1. Lighting

1.

Ensure that boiler is filled with water, air is bled

from boiler coil and that boiler water pressure is

at a minimum of 12 psi.

2.

Open main gas cock.

3.

Open gas cock on gas valve.

4.

Turn “ON” disconnect switch (on right side of

unit).

5.

After 45 seconds, ignition will occur (if there is a

call for heat).

9E-2. Shutdown

1.

Turn “OFF” disconnect switch.

2.

Close gas cock on gas valve.

3.

Close main gas cock.

SECTION 10.
Maintenance

10A. Owner Care and Maintenance

Inspect venting system - Annually remove

screws on vent terminal and remove terminal. Inspect

interior with flashlight.

General Housekeeping - Keep boiler area clear

and free from combustible materials, gasoline and

other flammable vapors and liquids.