Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 22

Advertising
background image

Page 22

LAARS Heating Systems

6.

Clean the finned tubing with a wire brush and

vacuum all loose material from the combustion

chamber.

7.

Replace all parts in the reverse order in which

they were removed.

8.

Restart the unit as indicated by the lighting

instruction label.

11C. Unit Pump

The unit pump operates whenever there is a call

for heat or hot water.

It is a wetted-rotor type pump and should always

be filled with water when it is operating so that it will

cool properly.

If a pump change is required for any reason,

valve off the boiler and drain approximately 1 or 2

gallons of water from the unit. Turn off the main

disconnect switch and unplug the pump wires, remove

the pump motor. The pump housing need not be

removed. The replacement pump motor should be

installed in the reverse order from which the old pump

motor was removed. After filling the system be sure to

bleed the coil.

NOTE: If the pump motor is not defective the

pump cartridge alone may be changed (Taco Pumps

Only).

11D. Gas Valve

The gas valve is a solenoid operated, negative

pressure regulated valve. The outlet pressure is

regulated at minus 0.2 inches w.c. It is designed to

operate with supply pressures of 4-13 inches w.c.

Within that range of supply pressures, the regulated

discharge pressure may vary from minus .05 to minus

.35 inches w.c. The regulator is not adjustable and the

effect of this variation in discharge pressure is not

significant. Because of the fixed regulator setting, gas

flow must be adjusted by changing the gas orifice.

To remove the gas valve, shut off 120 volt power

and the master gas cock in gas line, loosen the nut on

the gas orifice union and remove the orifice union plus

piping to the gas valve. Disconnect the wires from the

gas valve. The valve may now be unscrewed from the

inlet piping. It may be necessary to deflect the inlet

piping somewhat in order to clear the boiler jacket.

After the valve has been removed, replace with a new

valve in the reverse order in which the old valve was

removed. Do not over tighten the fittings into the

valve body as this may cause damage to the valve.

NOTE: When fueled by LP gas, H Series

perform best with 9-10 in. W.C. supply pressure. If no

other appliances are being supplied by the LP supply

set the low pressure regulator to 9-10 in. W.C.

11E. Safety Limit Switch

The Safety Limit Switch has a fixed set point at

215°F. It will reset automatically.

To replace the switch , shut off the 120 volt

power and valve off the boiler, drain 1 or 2 gallons of

water from the boiler and remove the nut which holds

the safety limit bulb in the boiler discharge fitting.

Remove the bulb from the fitting and remove the 2

screws which hold the switch assembly to the

electrical control box. Disconnect the 2 wires from the

quick connects at switch and remove the safety limit

assembly. To replace, perform the same operations in

reverse. Push the sensing bulb as far into the fitting as

possible before tightening sealing nut. No more than

1/2" of sensing bulb should be visible after

installation. Fill the boiler and be sure to bleed the coil

at the coil bleed petcock. Turn on disconnect switch

and check boiler operation.

11F. Operating Control

The Operating Control maintains boiler

discharge temperature between 170-210°F during the

space heating cycle. It has a fixed set point of 210°F

(HW-M2 Series only) and a differential of 40°F,

therefore, its contacts open at 210°F and they reclose

at 170°F. If replacement is necessary, shut off the 120

volt power and disconnect the wires to the sensor.

Valve off and drain 1 or 2 gallons of water from the

boiler and remove sensor. Install new sensor, refill

boiler and bleed coil at coil bleed petcock. Check

boiler operation after installation of new Operating

Control. The Operating Control on the H(P)-M2 series

has a fixed set point of 185°F. Its contacts open at

185°F and they reclose at 160°F.

11G. Igniter

The igniter is a “glow bar” type silicon carbide

unit. It is energized whenever there is a call for heat

and the red "IGNITER" light on the boiler control is

lit. After the igniter is switched off and the boiler

continues to run, the igniter functions as a flame

sensor for the boiler control.

If the ignitor fails and must be replaced, always

install a new igniter gasket with the replacement

igniter.

Caution

Ignitor gets hot.

11H. Pressure Differential Switch

The Pressure Differential Switch is a normally

open single pole switch which is designed to detect

pump operation and water flow. To replace, turn off

electrical power & boiler feed water. Valve off and

drain 1 or 2 gallons of water from the boiler, unplug

wires from the switch and remove switch. Install new

switch in reverse order. Refill boiler and bleed air

from the coil bleed petcock. Turn on electrical power

and recycle system.

OUT OF

PRODUCTION

Advertising