LAARS Heating Systems

RED “PURGE” Light flashing - blower or stack

switch failure or possible flue blockage.

RED “VALVE” Light flashing - valve, igniter

or flame sense failure (combustion related problem).

NOTE: If the stack switch contacts are closed

for any reason when the blower isn‘t operating a

sequence will not occur and after 45 seconds the

control will “lock out “ and the “PURGE” light will

flash. If the stack switch contacts are open and do not

close during purge period, after 5 minutes the control

will lock out and the “PURGE” light will flash.

If the boiler does not operate, the green “power”

light is on and no indicator lights are flashing, check

for an open pressure switch, low limit switch (on HW-

M2 series), operating control or safety limit switch on

either series. For additional troubleshooting

information refer to the trouble shooting flow charts

on the pages that follow.