SECTION 15.
Trouble Shooting

15A. S9301A Control Module

NORMAL SEQUENCE

FAILURE TO COMPLETE THIS CYCLE

Event

Control Funtion

Verified

Envent Confirmed

Light Event

Unconfirmed

Action for

Diagnosis

A. Power switch on

Integrated boiler control

(S9301A)

Green "POWER" light on.

Note: If internal pump is

running unit may be in

lockout. Reset power

switch.

1. No 120 VAC supply

1. Read voltage between

black & white wires at back

of (120 VAC) plug

2. Defective 24 VAC

transformer

2. Read voltage between

yellow wires at back of

(VAC 24XFMR) plug

3. Defective S9301A

module

3. Replace S9301A part

#2400-224

B. Prepurge (if low limit or

Thermostat calling)

2 - 17) secs)

1. Internal Pump Starts

Red "PURGE" light on.

Note: If unit in purge mode

without light, stack switch is

not proving air flow.

1. Internal pump defective

or air bound

1. Check for 120 VAC at

module pins marked

circulator (opposite brown

and white)

2. Low limit (HW-only),

operating control, safety

limit, system pressure

switch, stack switch

2. Defective low limit,

operating control, safety

limit or differential presssure

switch

2. Jump control wires, one

control at a time to identify

open circuit control, no

continuity.

3. Blower starts

3. Defective inducer blower

3. Check for 120 VAC at

module pins marked inducer

(opposite gray and white

wires)

C. Igniter heats up and

remains on (17 - 39 sec)

Igniter via S9301A

Red "IGNITER" light on

Red "PURGE" light off

Blower continues to run

Igniter does not heat up -

look for heat up at igniter

base

Check for 120 VAC at pins

marked IGNR (blue wires)

during igniter light "on"

D. Gas valve energized

(37 - 43 secs)

Gas valve opens

Red "VALVE/FLAME" light

on.

1. Stack switch does not

confirm air flow.

2. Gas valve has short.

Check for 24 VAC between

orange and yellow wires on

gas valve when red "VALVE

/ FLAME" light is on

E. Ignitor off (39 sec)

Gas valve energized

(39 - 43+ sec)

Igniter, air & gas source

Igniter monitors flame via

flame rectification to ground

Unit transfer to purge 12-15

secs after "valve / flame"

light is on and repeats

sequence

See trouble shooting

section under "cross

contamination" & "short

cycling" in service manual

OUT OF

PRODUCTION