Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 25

Advertising
background image

H Series

Page 25

the pressure to go positive (above 0 IN. W.C.). If the

pressure spikes positive when the solenoid opens then

the gas valve regulator is faulty and may be the cause

of the delayed ignition (assuming inlet tested OK).

A defective burner (flameholder) can cause a

delayed ignition however not often. If the gas supply

pressure and the gas valve are functioning properly

and the air and gas orifices are correct the burner

should be inspected. To inspect, remove the blower

and the burner will drop out of the bottom of the

chamber. There should be no perforations other than

the punched holes. When replacing the burner the

insulating pad must be on the top of it. If none was on

the burner when it was removed check to see if it fell

off during burner removal and has stayed in the

combustion chamber. Never leave an insulating pad

lying in the combustion chamber as this can cause

burner overheating and perforation.

12B. Noisy Operation

There are two principal sources of noisy

operation:
a.

Combustion - high pitched noise - whistle or hoot

b.

Boiling (kettling) - lower frequency noise which

varies with temperature - moan.
Combustion noise occurs at any boiler discharge

temperature and is heard the loudest at the flue outlet

(especially on units with side wall venting). There are

two basic causes for the noise, rich mixture and cross

contamination. To check for a rich mixture, it will be

necessary to measure the percent O² or CO² in the flue

products. O² readings lower than 4½ % or CO²

readings higher than 9¼% (natural gas) and 10.8%

(LP) will often cause combustion noise. To eliminate

the noise it will be necessary to install a smaller gas

orifice so that the O² will rise above 4½% or the CO²

will drop to 8½% (natural) or 9½% (LP).

Sometimes the readings are influenced by cross

contamination and a check for cross contamination

should be done before changing orifices if it is

suspected. A strong smell from the flue products is

generally an indication. Check for cross contamination

using the procedure listed in the index. If there is no

cross contamination, reorificing should be done.

Boiling (kettling) may occur at boiler discharge

temperatures from 170°F to 210°F. The temperature at

which it starts will vary from one installation to

another. The primary cause of the problem is poor heat

transfer on the inside of the boiler coil. This may be

caused by foaming of antifreeze in the system or

scaling from the boiler water if no antifreeze is

present.

There are many manufacturers of plumbing and

boiler antifreezes. Plumbing antifreezes should never

be used in a boiler system because they have no

antifoamants in them. Not all boiler antifreezes have

an effective antifoamant either so the noise may exist

with boiler antifreezes also.

The cure for the boiling noise is the same

regardless of the cause. However, if antifreeze in the

system is suspected of being the cause, the

concentration and type should be investigated before

attempting to eliminate the noise. The most effective

means of cleaning the combustion coil utilizes the

siphon cleaning method. Concentrations of antifreeze

should be kept as low as possible because antifreeze

will reduce heat transfer and efficiency.

Many times it is difficult to determine if the

noise is combustion or boiling related. The best clue is

when in the cycle the noise appears and if its

frequency changes with boiler discharge temperature.

Combustion noises always have the same frequency,

however, their volume may change from the time that

the burner first fires to the time that it shuts off.

Boiling noises have a frequency that varies with boiler

discharge temperature and sometimes they will

disappear completely at higher temperatures just

before the boiler goes off on limit. Vibration of the

boiler pressure gage needle may also occur with

boiling noises.

12C. Insufficient Hot Water

(HW - M2 - series only)

Possible Cause:

a.

No Flow Restrictor

b.

Low limit Failure

c.

Incorrect Wiring of System Circulator

d.

No Flow Check in System Supply

e.

Coil Contamination

The most common cause for insufficient hot

water complaints results from failure to install a flow

restrictor. If there is no flow restrictor water passes

through the coil at a greater volume than the boiler

output is capable of heating to the desired temperature

rise.

Failure of the low limit to operate within its

normal calibration points will have the same effect as

incorrect system circulator wiring.

Incorrect wiring for the system circulator can

also cause the problem. If the blue wire in the field

wiring box is not used to control the circulator or

circulators then the low limit cannot prevent boiler

water temperature from dropping to a point that is

insufficient to provide enough heat for the domestic

hot water coil. The blue wire interrupts power to the

system circulator through the priority relay R-1. R-1 is

controlled by the low limit which should limit

minimum tank temperature to 140°F.

Flow checks in single zone systems and

multizone systems with zone circulators prevent

gravity circulation of heated boiler water from the

OUT OF

PRODUCTION

Advertising