Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 32

Advertising
background image

Page 32

LAARS Heating Systems

Figure 27. Checking Blower (You Must Complete Figure 26 First).

RESET BOILER CONTROL BY
SWITCHING BOILER SWITCH OFF
FOR 15 SECS, THEN BACK ON.

REFER TO GENERAL TROUBLE
SHOOTING SECTION FIGURE 24

CONNECT MANOMETER TO "PRESSURE TAP"
ON GAS VALVE - PRESSURE DURING BLOWER
OPERATION WITHOUT GAS FLOW (VALVE
LIGHT NOT LIT) IS - 2.5 IN W.C.

CHECK FOR VOLTAGE 120 VAC
AT BLOWER WIRE CONNECTOR
(WITHIN 5 MINS. AFTER GREEN
LIGHT)

BLOWER O.K.

CHECK FOR FLUE
OBSTRUCTIONS

BLOWER STARTS

YES

YES

NO

YES

NO

NO

REPLACE BLOWER

0 VOLTS

120 VAC

CHECK TT, LIMITS,
STACK SWITCH

REPLACE BOILER
CONTROL 2400-224

REFER TO FIGURE 25
REFER TO FIGURE 28

OK

OPEN

Р

Р

Р

Р

Р

Р

Р

Р

Р

Р

Р

WITH A CALL FOR HEAT / HOT WATER, AFTER TWO
SECONDS DOES GREEN POWER LIGHT COMES ON.

REPLACE
BLOWER

CLEAR / REMOVE
OBSTRUCTION

Ð

CLEAR

OBSTRUCTED

Ð

OUT OF

PRODUCTION