Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 34

Advertising
background image

Page 34

LAARS Heating Systems

Figure 29. Red "Valve/Flame" Light Flashing (You Must Complete Figure 24 First).

RESET BOILER BY INTERUPTING POWER FOR 15
SECONDS - WHEN "VALVE/FLAME" LITE LIGHTS
IS THERE 24 VAC BETWEEN ORANGE AND
YELLOW WIRES ON GAS VALVE AND/OR DOES
GAS VALVE CLICK?

TURN ON VALVES, FILL LP TANK ON LP
UNIT. RESET BOILER BY SWITCHING
POWER OFF FOR 15 SECONDS. RUN
THROUGH TWO TO THREE CYCLES

CHECK WIRES TO GAS VALVE

DOES BURNER IGNITE AND
APPEAR TO RUN PROPERLY?

NUISANCE LOCKOUT CAUSED FLASHING
LITE - CHECK COMBUSTION

CHECK IGNITER-
IGNITER OK?
50 - 150 OHMS,
NO CRACKS.

REPLACE
INTEGRATED
BOILER
CONTROL
P\N 2400-224

CORRECT
WIRING

REPLACE
IGNITER

REPLACE INTEGRATED BOILER CONTROL P/N 2400-224

INSTALL
CORRECT
ORIFICES

BOILER CYCLES THROUGH THREE CYCLES AFTER
RESETTING AND “VALVE” LITE FLASHES

CHECK GAS AND AIR ORIFICE
FOR PROPER SIZE

REPLACE GAS VALVE

ARE GAS VALVES AND GAS METER TURNED ON.
IS THERE GAS IN LP TANK (LP UNITS).

YES

YES

YES

NO

OK

FAULTY

NO

INCORRECT

CORRECT

NO

Р

Р

Р

Р

Р

Р

Р

Р

Р

Р

CHECK FOR GAS FLOW.
IS METER MOVING?
(GAS PRESSURE IS OK)

Р

Р

YES

NO

Р

Р

Р

YES

NO

OUT OF

PRODUCTION