Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 29

Advertising
background image

H Series

Page 29

PURGE - SEE FIGURE 26
VALVE SEE FIGURE 28

1. LIMIT CIRCUIT OPEN

SEE FIGURE 25

2. NO CALL FOR HEAT/

HOT WATER

REPLACE BOILER
CONTROL
2400-224

REPLACE TRANSFORMER
AND RUN BOILER
THROUGH A FEW CYCLES

HAVE QUALIFIED
ELECTRICIAN
REPAIR FAULT IN
WIRING TO THE
BOILER

CHECK FOR VOLTAGE (24
VAC) BETWEEN YELLOW
WIRES AT BACK OF "VAC
24 XFMR" CONNECTOR
ON BOILER CONTROL

1. IS SERVICE SWITCH ON?
2. IS CIRCUIT ON?
3. ARE FUSES OR CIRCUIT

BREAKER OK?

CORRECT AND
RECYCLE BOILER
THROUGH A FEW
CYCLES

CHECK FOR VOLTAGE
(120 VAC) BETWEEN
BLACK AND WHITE
WIRES AT BACK OF "120
VAC" CONNECTOR ON
BOILER CONTROL

DID BOILER RUN THROUGH
A COMPLETE CYCLE AS
DESCRIBED IN SEQUENCE
OF EVENTS ON PAGE 25

PUMP OPERATES
(120 V TO PUMP)

REFER TO
FIGURE 30

YES

NO

YES

NO

0 VOLTS

120
VOLTS

0
VOLTS

24
VOLTS

* POOR SWITCH CONTACT ON RELAYS, ZONE VALVES, OR THERMOSTATS CAN CAUSE A FLASHING GREEN
LIGHT ON JOHNSON CONTROLS G856DBG - 5201.

AFTER 5 MINUTES ARE ANY
RED LIGHTS FLASHING

YES

NO

REFER TO FLOW
CHART FOR SPECIFIC
PROBLEM

YES

GREEN LIGHT COMES ON

О

Р

RESET BOILER CONTROL BY INTERRUPTING

POWER AT SIDE OF UNIT FOR 15 SECONDS

Р

Р

NO

Р

Р

Р

Р

Р

YES

Р

Р

Р

Р

О

О

NO

Figure 24. General Trouble Shooting.