8.8 EARTH FAULT SHUTDOWN / ELECTRICAL TRIP ALARM


When the module is suitably connected using the ‘Earth Fault CT’. The module measures Earth Fault and can
optionally be configured to generate an alarm condition (shutdown or electrical trip) when a specified level is
surpassed.

If the Earth Fault alarm is enabled, the controller begins following the IDMT ‘curve’. If the Trip is surpassed for an
excess amount of time the Alarm triggers (Shutdown or Electric trip as selected in Action).

The higher the Earth Fault, the faster the trip. The speed of the trip is dependent upon the fixed formula :

T = K x 0.14 / ((I / I

s

)

0.02

-1)


Where:

T is the tripping time in seconds (accurate to +/- 5% or +/- 50ms (whichever is the greater)
K is the time multiplier setting
I is the actual earth current measured

I

s

is the trip setting value





The settings shown in the example above are a screen capture of the DSE factory settings, taken from the DSE
Configuration Suite software.

I

S

(Trip setting

value)

K (time multiplier setting)