DSE7200 / 7300 Series Operators Manual

115

SYMPTOM

POSSIBLE REMEDY

Incorrect reading on Engine
gauges

Fail to stop alarm when engine is
at rest

Check engine is operating correctly. Check sensor and wiring paying
particular attention to the wiring to terminal 47 (refer to appendix). Check that
sensor is compatible with the 7000 series module and that the module
configuration is suited to the sensor.

Module appears to ‘revert’ to an
earlier configuration

When editing a configuration using the PC software it is vital that the
configuration is first ‘read’ from the controller before editing it. This edited
configuration must then be “written” back to the controller for the changes to
take effect.

When editing a configuration using the fascia editor, be sure to press the

Accept

button to save the change before moving to another item or

exiting the fascia editor

Set will not take load

Ensure the generator available LED is lit

Check that the output configuration is correct to drive the load switch device
and that all connections are correct.

Remember that the set will not take load in manual mode unless a remote
start on load input is present or the close generator button is pressed.

Inaccurate generator
measurements on controller
display

Check that the CT primary, CT secondary and VT ratio settings are correct for
the application.

Check that the CTs are wired correctly with regards to the direction of current
flow (p1,p2 and s1,s2) and additionally ensure that CTs are connected to the
correct phase (errors will occur if CT1 is connected to phase 2).

Remember to consider the power factor. Ie (kW = kVA x powerfactor)

The 7000 series controller is true RMS measuring so gives more accurate
display when compared with an ‘averaging’ meter such as an analogue panel
meter or some lower specified digital multimeters.

Accuracy of the controller is better than 1% of full scale. Ie Gen volts full
scale is 333V ph-n so accuracy is ±3.33V (1% of 333V).


NOTE:- The above fault finding is provided as a guide check-list only. As the module can be

configured to provide a wide range of different features, always refer to the source of your module
configuration if in doubt.