DSE7200 / 7300 Series Operators Manual

110

8.13.2 ADJUSTABLE PARAMETERS

Front Panel Configuration Editor

= Only available on DSE7220 / DSE7320 AMF Modules

Section

Parameter as shown on display

Settings

DISPLAY

Contrast

0%

Language

English

LCD Page Timer

0h 0m 0s

Auto Scroll Delay

0h 0m 0s

Current Date and time

hh:mm

EDITOR

Alt Config

Default Config

ENGINE

Oil Pressure Low Shutdown

0.00bar

Oil Pressure Low Pre Alarm

0.00bar

Coolant Temperature Low Warning

0ºC (If Configured)

Coolant Temperature High Pre Alarm

0ºC

Coolant Temperature High Shutdown

0ºC

Start Delay Off Load

0h 0m 0s

Start Delay On Load

0h 0m 0s

Start Delay Mains Fail

0h 0m 0s

Start Delay Telemetry

0h 0m 0s

Pre Heat Timer

0h 0m 0s

Crank Duration Timer

0m 0s

Crank Rest Timer

0m 0s

Safety On Delay

0m 0s

Smoke Limiting

0m 0s

Smoke Limiting Off

0m 0s

Warm Up Timer

0m 0s

Cool Down Time

0h 0m 0s

Engine Under Speed Shutdown

Active / Inactive

Engine Under Speed Shutdown

0 rpm

Engine Under Speed Warning

Active / Inactive

Engine Under Speed Warning

0 rpm

Engine Over Speed Warning

Active / Inactive

Engine Over Speed Warning

0 rpm

Engine Over Speed Shutdown

0 rpm

Engine Speed Overshoot Delay

0m 0s

Engine Speed Overshoot

0%

Fail To Stop Delay

0m 0s

Battery Under Voltage Warning

Active / Inactive

Battery Under voltage Warning Delay

0h 0m 0s

Battery Under Voltage

0 V

Battery Over Voltage Warning

Active / Inactive

Battery Over Voltage Warning Delay

0h 0m 0s

Battery Over Voltage Warning

0 V

Charge Alternator Failure Warning

Active / Inactive

Charge Alternator Failure Warning

0 V


Charge Alternator Warning Delay

0h 0m 0s

Charge Alternator Failure Shutdown

Active / Inactive

Charge Alternator Failure Shutdown

0.0 V

Charge Alternator Shutdown Delay

0h 0m 0s

DPTC Auto Regeneration Inhibit

Active / Inactive

Fuel Usage Alarm (Running Rate)

0% - 100%

Fuel Usage Alarm (Stopped Rate)

0% - 100%

Droop control

Active / Inactive

Droop control

0%

GENERATOR

Generator Under Voltage Shutdown

0 V

Generator Under Voltage Pre Alarm

0 V

Generator Nominal Voltage

0 V

Generator Over Voltage Pre Alarm

0 V

Generator Over Voltage Shutdown

0 V

Generator Under Frequency Shutdown

0 Hz

Generator Under Frequency Pre Alarm

0 Hz

Generator Nominal Frequency

0 Hz

Generator Over Frequency Pre Alarm

0 Hz

Generator Over Frequency Shutdown

0 Hz

Full Load Rating

0 A

KW Overload Trip

0%

Delayed Over Current

Active / Inactive

Delayed Over Current

0%

AC System

3 Phase, 4 Wire

CT Primary

0 A

CT Secondary

0 A

Generator transient delay

0s

MAINS

Mains Under Voltage Trip

0 V

Mains Over Voltage Trip

0 V

Mains Under Frequency Trip

0 Hz

Mains Over Frequency Trip

0 Hz

Mains Over Frequency Trip

0 Hz