3 magnetic pickup, can and expansion – Winco DSE7300 Series User Manual

Page 34

Advertising
background image

DSE7200 / 7300 Series Operators Manual

34

4.2.3 MAGNETIC PICKUP, CAN AND EXPANSION

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

22

Magnetic pickup Positive

0.5mm²

AWG 20

Connect to Magnetic Pickup device

23

Magnetic pickup Negative

0.5mm²

AWG 20

Connect to Magnetic Pickup device

24

Magnetic pickup screen

Shield

Connect to ground at one end only

25

CAN port H

0.5mm²

AWG 20

Use only 120Ω CAN approved cable

26

CAN port L

0.5mm²

AWG 20

Use only 120Ω CAN approved cable

27

CAN port Common

0.5mm²

AWG 20

Use only 120Ω CAN approved cable

28

+

0.5mm²

AWG 20

Use only 120Ω RS485 approved cable

29

-

0.5mm²

AWG 20

Use only 120Ω RS485 approved cable

30

SCR

0.5mm²

AWG 20

Use only 120Ω RS485 approved cable

NOTE:- Terminals 31 to 38 are not fitted to the 7200 / 7300 controller

NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is

earthed at one end ONLY.

NOTE:- Screened 120

impedance cable specified for use with CAN must be used for the CAN link

and the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120

impedance cable suitable for CAN

use (DSE part number 016-030)

NOTE:- When the module is configured for CAN operation, terminals 22, 23 & 24 should be left

unconnected. Engine speed is transmitted to the 7000 series controller on the CAN link.
Refer to Electronic Engines and DSE Wiring
for further information. Part No. 057-004.