DSE7200 / 7300 Series Operators Manual

14

3.8 INPUTS

3.8.1 DIGITAL INPUTS

Number

DSE7200

6

DSE7300

8

Arrangement

Contact between terminal and ground

Low level threshold

2.1V minimum

High level threshold

6.6V maximum

Maximum input voltage

+50V DC with respect to plant supply negative

Minimum input voltage

-24V DC with respect to plant supply negative

Contact wetting current

7mA typical

Open circuit voltage

12V typical


3.8.2 ANALOGUE INPUTS

3.8.2.1 OIL PRESSURE


Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

15mA

Full scale

240Ω

Over range / fail

270Ω

Resolution

1-2 PSI / 0.1 Bar

Accuracy

±2% of full scale resistance (±4.8Ω) excluding transducer error

Max common mode
voltage

±2V

Display range

0-200 PSI / 13.7 bar subject to limits of the sensor


3.8.2.2 COOLANT TEMPERATURE


Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

10mA

Full scale

480Ω

Over range / fail

540Ω

Resolution

1°C, 2°F

Accuracy

+/-2% of full scale resistance (±9.6Ω) excluding transducer error

Max common mode
voltage

±2V

Display range

0°C -140°C, 32°F - 284°F Depending on sensor