4.3.4 7320 AMF CONTROLLER


3 phase, 4 wire with restricted earth fault protection

NOTE:- Earthing the neutral conductor ‘before’ the neutral CT allows the module to read earth faults

‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults ‘before’ the CT
only (Restricted to generator / upstream of the CT)