Winco DSE7300 Series User Manual

Page 15

Advertising
background image

DSE7200 / 7300 Series Operators Manual

15

3.8.2.3 FUEL LEVEL


Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

10mA

Full scale

480Ω

Over range / fail

540Ω

Resolution

1%

Accuracy

+/-2% of full scale resistance (±9.6Ω) excluding transducer error

Max common mode
voltage

±2V

Display range

0-250%


3.8.2.4 FLEXIBLE SENSOR

NOTE : Flexible sensor is not available on DSE7200 series controllers


Measurement type

Resistance measurement by measuring voltage across sensor with a fixed current
applied

Arrangement

Differential resistance measurement input

Measurement current

10mA

Full scale

480Ω

Over range / fail

540Ω

Resolution

1%

Accuracy

+/-2% of full scale resistance (±9.6Ω) excluding transducer error

Max common mode
voltage

±2V

Display range

0-250%


3.8.3 CHARGE FAIL INPUT


Minimum voltage

0V

Maximum voltage

35V (plant supply)

Resolution

0.2V

Accuracy

± 1% of max measured voltage (±0.35V)

Excitation

Active circuit constant power output

Output Power

2.5W Nominal @12V and 24V

Current at 12V

210mA

Current at 24V

104mA





Advertising