DSE7200 / 7300 Series Operators Manual

12

3.6 GENERATOR AND MAINS VOLTAGE / FREQUENCY SENSING

3.6.1 GENERAL


Measurement type

True RMS conversion

Sample Rate

5KHz or better

Harmonics

Up to 10

th

or better

Input Impedance

300K Ω ph-N

Common mode offset from Earth

100V AC (max)


3.6.2 VOLTAGE SENSING

See section entitled Part Numbering elsewhere in this document to identify the Hardware Version of the controller
you are using.


3.6.2.1 MODEL HARDWARE VERSION 001 TO 006


Phase to Neutral

15V

(minimum required for sensing frequency

)

to 333V AC

(absolute maximum)

Suitable for 110V to 277V nominal

(±20% for under/overvoltage detection)

Phase to Phase

26V

(minimum required for sensing frequency

)

to 576V AC

(absolute maximum)

Suitable for 190V ph-ph to 479V ph-ph nominal

(±20% for under/overvoltage detection)

Resolution

1V AC phase to neutral
2V AC phase to phase

Accuracy

±1% of full scale phase to neutral
±2% of full scale phase to phase


3.6.2.2 MODEL HARDWARE VERSION 007 ONWARDS

Phase To Neutral

15V

(minimum required for sensing frequency

)

to 415V AC

(absolute maximum)

Suitable for 345V nominal

(±20% for under/overvoltage detection)

Phase To Phase

25V

(minimum required for sensing frequency

)

to 720V AC

(absolute maximum)

Suitable for 600V nominal

(±20% for under/overvoltage detection)

Resolution

1V AC phase to neutral
2V AC phase to phase

Accuracy

±1% of full scale phase to neutral
±2% of full scale phase to phase


3.6.3 FREQUENCY SENSING

Minimum frequency

3.5Hz

Maximum frequency

75.0Hz

Frequency resolution

0.1Hz

Frequency accuracy

±0.2Hz