Winco DSE7300 Series User Manual

Page 95

Advertising
background image

DSE7200 / 7300 Series Operators Manual

95

8.3 WARNINGS


Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.

Example

Alarm 1/1

Charge Failure
Warning


In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and
shutdowns.

By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings
are latched’ will cause warning alarms to latch until reset manually. This is enabled using the 7000 series
configuration suite in conjunction with a compatible PC.

Display

Reason

CHARGE FAILURE

The auxiliary charge alternator voltage is low as measured from the W/L terminal.

BATTERY UNDER
VOLTAGE

The DC supply has fallen below the low volts setting level for the duration of the
low battery volts timer

BATTERY OVER VOLTAGE

The DC supply has risen above the high volts setting level for the duration of the
high battery volts timer

FAIL TO STOP

The module has detected a condition that indicates that the engine is running
when it has been instructed to stop.

NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor or

switch - If the engine is at rest check oil sensor wiring and configuration.

FUEL USAGE

Indicates the amount of fuel measured by the fuel level sensor is in excess of the
Fuel Usage alarm settings. This often indicates a fuel leak or potential fuel theft.

AUXILIARY INPUTS

Auxiliary inputs can be user configured and will display the message as written by
the user.

LOW FUEL LEVEL

The level detected by the fuel level sensor is below the low fuel level setting.

kW OVERLOAD

The measured Total kW is above the setting of the kW overload warning alarm

EARTH FAULT
(DSE7300 series V2.0 or
above only)

The measured Earth Fault Current has been in excess of the earth fault trip and
has surpassed the IDMT curve of the Earth Fault alarm.

NEGATIVE PHASE
SEQUENCE
(DSE7000 series V2.0 or
above only)

Indicates ‘out of balance’ current loading of the generator.
Sometimes also called Negative Sequence Current or Symmetry Fault

MAINTENANCE DUE
(DSE7000 series V2.1 or
above only)

Indicates that the maintenance alarm has triggered. A visit is required by the
Generator service company.

LOADING VOLTAGE NOT
REACHED

Indicates that the generator voltage is not above the configured loading voltage.
The generator will not take load when the alarm is present after the safety timer.

LOADING FREQUENCY
NOT REACHED

Indicates that the generator frequency is not above the configured loading
frequency.
The generator will not take load when the alarm is present after the
safety timer.

Advertising
This manual is related to the following products: