3.12 DSENET® FOR EXPANSION MODULES


DSENet® is the interconnection cable between the host controller and the expansion module(s) and must not be
connect to any device other than DSE equipment designed for connection to the DSENet®

NOTE: DSENet® is not available on DSE7200 series controllers.


Cable type

Two core screened twisted pair

Cable characteristic impedance

120Ω

Recommended cable

Belden 9841
Belden 9271

Maximum cable length

1200m (¾ mile) when using Belden 9841 or direct equivalent.
600m (666 yds) when using Belden 9271 or direct equivalent.

DSENet® topology

“Daisy Chain” Bus with no stubs (spurs)

DSENet® termination

120Ω. Fitted internally to host controller. Must be fitted externally to the ‘last’
expansion module by the customer.

Maximum expansion modules

Refer to host controller documentation.

NOTE : As a termination resistor is internally fitted to the host controller, the host controller must be

the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the ‘last’ unit on the DSENet®. For
connection details, you are referred to the section entitled ‘typical wiring diagram’ elsewhere in this
document.

3.12.1 DSENET® USED FOR MODBUS ENGINE CONNECTION


As DSENet® utilises an RS485 hardware interface, this port can be configured for connection to Cummins
Modbus engines (Engines fitted with Cummins GCM (Generator Control Module)).
This leaves the RS485 interface free for connection to remote monitoring equipment (i.e. Building Management
System, PLC or PC RS485 port).

While this is a very useful feature in some applications, the obvious drawback is that the DSENet® interface is no
longer available for connection to expansion devices.

Example of configuring the DSENet® for connection to Cummins QST GMC using the DSE Configuration Suite
Software: