DSE7200 / 7300 Series Operators Manual

98

Display

Reason

GENERATOR OVER FREQUENCY

The generator output frequency has risen above the preset level

GENERATOR UNDER FREQUENCY

The generator output frequency has fallen below the preset level

GENERATOR OVER VOLTAGE

The generator output voltage has risen above the preset level

GENERATOR UNDER VOLTAGE

The generator output voltage has fallen below the preset level

OIL PRESSURE SENSOR OPEN
CIRCUIT

The oil pressure sensor is detected as not being present (open circuit)

AUXILIARY INPUTS

An active auxiliary input configured as a shutdown will cause the engine
to shut down. The display shows the text as configured by the user.

LOSS OF SPEED SIGNAL

The speed signal from the magnetic pickup is not being received by the
DSE controller.

ECU DATA FAIL

The module is configured for CAN operation and does not detect data on
the engine Can datalink, the engine shuts down.

ECU SHUTDOWN

The engine ECU has detected a shutdown alarm and has informed the
DSE module of this situation. The exact error is also indicated on the
module’s display.

kW OVERLOAD

The measured Total kW is above the setting of the kW overload
shutdown alarm

NEGATIVE PHASE SEQUENCE
(DSE7000 series V2.0 or above
only)

Indicates ‘out of balance’ current loading of the generator.
Sometimes also called Negative Sequence Current or Symmetry Fault

MAINTENANCE DUE
(DSE7000 series V2.1 or above
only)

Indicates that the maintenance alarm has triggered. A visit is required by
the Generator service company.

GENERATOR HIGH CURRENT

A High Current condition has continued for an excess period, then the
alarm escalates to either a shutdown or electrical trip condition
(depending upon module configuration). For further details of the high
current alarm, please see High Current Shutdown / Electrical Trip Alarm.

LOADING VOLTAGE NOT
REACHED

Indicates that the generator voltage is not above the configured loading
voltage
after the safety timer. The generator will shutdown.

LOADING FREQUENCY NOT
REACHED

Indicates that the generator frequency is not above the configured
loading frequency after the safety timer. The generator will shutdown.

PROTECTIONS DISABLED

Shutdown and electrical trip alarms can be disabled by user
configuration. In this case, Protections Disabled will appear on the
module display; The alarm text will be displayed but the engine will
continue to run. This is ‘logged’ by the module to allow DSE Technical
Staff to check if the protections have been disabled on the module at any
time. This feature is available from V4 onwards.

POSITIVE VAr

Positive VArs has exceeded the trip settings.

NEGATIVE VAr

Negative VArs has exceeded the trip settings.