DSE7200 / 7300 Series Operators Manual

35

4.2.4 LOAD SWITCHING AND GENERATOR VOLTAGE SENSING

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

39

Output relay C

1.0mm

AWG 18

Normally configured to control mains contactor coil
(Recommend 10A fuse)

40

Output relay C

1.0mm

AWG 18

Normally configured to control mains contactor coil

41

Output relay D

1.0mm

AWG 18

Normally configured to control generator contactor coil
(Recommend 10A fuse)

42

Output relay D

1.0mm

AWG 18

Normally configured to control generator contactor coil

43

Generator L1 (U) voltage monitoring

1.0mm²

AWG 18

Connect to generator L1 (U) output (AC)
(Recommend 2A fuse)

44

Generator L2 (V) voltage monitoring
input

1.0mm²

AWG 18

Connect to generator L2 (V) output (AC)
(Recommend 2A fuse)

45

Generator L3 (W) voltage monitoring
input

1.0mm²

AWG 18

Connect to generator L3 (W) output (AC)
(Recommend 2A fuse)

46

Generator Neutral (N) input

1.0mm²

AWG 18

Connect to generator Neutral terminal (AC)

NOTE:- The above table describes connections to a three phase, four wire alternator. For alternative

wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.


4.2.5 MAINS VOLTAGE SENSING

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

47

Mains L1 (R) voltage monitoring

1.0mm

AWG 18

Connect to Mains L1 (R) incoming supply (AC)
(Recommend 2A fuse)

48

Mains L2 (S) voltage monitoring

1.0mm

AWG 18

Connect to Mains L1 (S) incoming supply (AC)
(Recommend 2A fuse)

49

Mains L3 (T) voltage monitoring

1.0mm

AWG 18

Connect to Mains L1 (T) incoming supply (AC)
(Recommend 2A fuse)

50

Mains Neutral (N) input

1.0mm

AWG 18

Connect to Mains N incoming supply (AC)

NOTE:- Terminals 47-50 are not fitted to the 7210 / 7310 controller.