Winco DSE7300 Series User Manual

Page 16

Advertising
background image

DSE7200 / 7300 Series Operators Manual

16

3.8.4 MAGNETIC PICKUP


Type

Differential input

Minimum voltage

0.5V RMS

Max common mode voltage

±2V

Maximum voltage

Clamped to ±70V by transient suppressers, dissipation not to exceed 1W.

Maximum frequency

10,000Hz

Resolution

6.25 RPM

Accuracy

±25 RPM

Flywheel teeth

10 to 500

NOTE : DSE can supply a suitable magnetic pickup device, available in two body thread lengths :

DSE Part number 020-012 - Magnetic Pickup probe 5/8 UNF 2½” thread length
DSE Part number 020-013 - Magnetic Pickup probe 5/8 UNF 4” thread length


Magnetic Pickup devices can often be ‘shared’ between two or more devices. For example, one device can often
supply the signal to both the DSE7000 series module and the engine governor. The possibility of this depends
upon the amount of current that the magnetic pickup can supply.

3.9 OUTPUTS

3.9.1 OUTPUTS A & B


Type

Normally used for Fuel / Start outputs. Fully configurable for other purposes if the module is configured
to control an electronic engine. Supplied from Emergency Stop terminal 3.

Rating

15A resistive @ 35V


3.9.2 OUTPUTS C & D


Type

Voltage free relays, fully configurable, normally used for generator / mains load switch control.

Rating

8A resistive @ 250 V AC


3.9.3 OUTPUTS E,F,G & H


Type

Fully configurable, supplied from DC supply terminal 2.

Rating

2A resistive @ 35V


Advertising