ADLINK DAQe-2214 User Manual

Page 68

Advertising
background image

56

Operation Theory

In stop mode II, after a software stop command is given, the wave-
form generation does not stop until a complete single waveform is
finished. See Figure 4-19. Since the UC_counter is set to four, the
total DA update counts (number of pulses of DAWR signal) must
be a multiple of four (update counts = 20 in this example).

Figure 4-19: Stop Mode II

In stop mode III, after a software stop command is given, the
waveform generation does not stop until the performed number
of waveforms is a multiple of the IC_Counter. See Figure 4-20.
Since the IC_Counter is set to three, the total generated wave-
forms must be a multiple of three (waveforms = 6 in this exam-
ple), and the total DA update counts must be a multiple of 12
(UC_counter * IC_Counter). You can compare these three fig-
ures to see the differences.

Figure 4-20: Stop Mode III

Advertising