Auxiliary function inputs (afi), Table 4-7: auxiliary function input signals and, Functionalities – ADLINK DAQe-2214 User Manual

Page 85

Advertising
background image

Operation Theory

73

Auxiliary Function Inputs (AFI)

You can use the AFI in applications that take advantage of exter-
nal circuitry to directly control the DAQ-/DAQe-2213/2214 card.
The AFI includes two categories of timing signals: one group is the
dedicated input, and the other is the multi-function input. Table 4-7
illustrates this categorization.

Category Timing signal

Functionality

Constraints

Dedi-

cated

input

EXTTIMEBASE

Replace the

internal TIME-

BASE

• TTL-compatible
• 1 MHz to 40 MHz
• Affects on both A/D and D/A

operations.

EXTDTRIG

External digital

trigger input for

A/D operation

• TTL-compatible
• Minimum pulse width = 20ns
• Rising edge or falling edge

EXTWFTRG

(for DAQ-DAQe-

2214 only)

External digital

trigger input for

D/A operation

• TTL-compatible
• Minimum pulse width = 20ns
• Rising edge or falling edge

Multi-

function

input

AFI[0]

(Dual-functions)

Replace the

internal

ADCONV

• TTL-compatible
• Minimum pulse width = 20ns
• Rising–edge sensitive only

Replace the

internal

SCAN_START

• TTL-compatible
• Minimum Pulse width > 2/

TIMEBASE

AFI[1]

(for DAQ-DAQe-

2214 only)

Replace the

internal DAWR

• TTL-compatible
• Minimum pulse width = 20ns
• Rising–edge sensitive only

Table 4-7: Auxiliary Function Input Signals and Functionalities