9.2 Flue

confi guration description

9.2.1 Horizontal

concentric

fl ue Ø 60/100 mm

or Ø 80/125 mm (C13 type installation)

a

DANGER:

If necessary, you must install a terminal protection kit.

Ø 60/100 mm

L

63

1

Key

1 Gasket (fi tted)

Ø 80/125 mm

L

1

Key

1 Gasket (fi tted)

Type

Max length

Ø 60/100

6 m

Ø 80/125

10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.

When using the Plume Management Kit, the maximum lengths

fl ue pipe A and B (60/100mm) are:

A (m) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5
B (m) 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5

Refer to the Plume Management Kit installation manual.

9.2.2 Vertical

concentric

fl ue Ø 60/100 mm

or Ø 80/125 mm (C33 type installation)

L

Type

Max length (L)

Ø 60/100

6 m

Ø 80/125

10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.

INSTALLATION