Maintenance – Glow-worm Ultimate c User Manual

Page 39

Advertising
background image

0020167175_01 - 02/13 - Glow-worm

17.6 Expansion

vessel

1

2

Key

1 Expansion

vessel

2 Expansion vessel pressure inlet

•

Check the expansion vessel's supply pressure (see « Technical

Data » chapter) by means of the pressure inlet located on the

expansion vessel. Adjust the pressure if necessary.

•

Following the installation of a new expansion vessel, fi ll and

purge the appliance or installation, if necessary.

17.7 Condensate

trap

a

Warning:

condensate is mildly acidic. Use protective gloves.

5

3

2

4

1

6

Key

1 Condensate cleaning cap

2 Condensate

pipe

3 Condensate

outletv

4 Condensate retaining screw

5 Condensate

trap

6 Hose

•

Place a container under the condensate trap (5).

•

Remove the condensate from the reservoir (1).

•

Disconnect the condensation discharge (2).

•

Disconnect the heat exchanger hose (6).

The condense trap will contain water, lift taking care not to spill

the water.

•

Remove the condensate trap (5) using the retaining screw (4).

•

Clean the hose, the trap and the siphon, remove any

accumulated dirt.

•

Reassemble the components, taking care to position the

gaskets correctly.

•

Start the siphon (3) and fi ll with water.

MAINTENANCE

- 37 -

Advertising