Maintenance, 16 draining, 17 servicing – Glow-worm Ultimate c User Manual

Page 35

Advertising
background image

0020167175_01 - 02/13 - Glow-worm

Compare the value measured with the values indicated in the

table below.

Gas adjustment

G20

G31

CO

2

case ON

9 ± 0.2 %

10.1 ± 0.2 %

CO

2

case OFF

9.2 ± 0.3 %

10.3 ± 0.3 %

i

IMPORTANT:

Safe combustion can only be verifi ed by measuring CO/

CO

2

ratio. This must not exceed the value shown in the

table under the section "Maximum Rate and Adjustment".

15.1.3 Restarting

Replace the cap

Replace the appliance front panel.

Note: following the replacement of the front panel, the CO

2

value

will change: you can check that the value "case on" is correct by

the values in the previous table.

1

2

Key

1 Serial number stickers

2 Data label location

Firmly attach the gas replacement label to the appliance in the

corresponding location (1) on the electrical box.

15.2 Restart - re-check commissioning

Before putting the appliance into operation, follow the

instructions within the chapter Specifi c adjustment.

16 Draining

16.1 Heating

circuit

B

A

1

2

2

Key

1 Length of hose (not supplied)

2 Drain

valve

Drain down the heating circuit of the boiler only, by closing

the heating fl ow and return isolating valves. See chapter

"Hydraulic connection > Gas and water connections"

Open the drain point (2). Attach a length of hose (1) if

required.

After draining, close the drain valve (2) and remove the hose.

16.2 Domestic Hot water circuit

Drain the Domestic Hot Water circuit by closing the cold-water

isolation valve.

Open one or more hot water taps to drain the hot water circuit.

17 Servicing

To ensure the continued effi cient and safe operation of the

boiler it is recommended that it is checked and serviced as

necessary at regular intervals.

The frequency of servicing will depend upon the particular

installation conditions and usage. However it is recommended

that the boiler is inspected as part of a service at least once a

year.

If this appliance is installed in a rented property there is a duty of

care imposed on the owner of the property by the current issue of

the Gas Safety (Installation and Use) Regulations, Section 35.

Servicing/maintenance should be carried out by a competent

person approved at the time by the Health and Safety

Executive in accordance with the rules in force in the countries

of destination.

MAINTENANCE

- 33 -

Advertising