Maintenance – Glow-worm Ultimate c User Manual

Page 32

Advertising
background image

0020167175_01 - 02/13 - Glow-worm

Fault

codes Description

Cause

Solution

F61

Fault in the main board

Gas valve command fault

• Check the main boards connections.

• Check the main board.

• Check the appliance DSN number is correct.

• Reset the appliance.

F62

Gas valve closure fault

F63

Fault in the main board memory

F64

Rapid fl uctuation of return or fl ow heating

sensor.

F65

Excessive main board temperature

F67

Flame signal fault in the main board

F68

Fluctuation of fl ame signal

No return gas / Insuffi cient gas fl ow

Gas valve incorrectly adjusted

Defective fi ring electrode and fl ame control /

Defective igniter unit

• Check the return gas circuit (gas valve open).

• Check the observe the fl ame picture and check the

CO

2

setting.

• Check the igniter unit connections.

• Check the state of the electrode (corrosion).

F70

User interface incompatible with the

main board

Incorrect product code

• Check that the appliance DSN code on the screen

matches the product code of the nameplate (in the

event of a fault and the appliance DSN does not

appear, consult menu.d.93 reserved for the code).

• Check the boards reference.

F71

Flow heating temperature sensor fault

Flow heating temperature sensor unclipped

or defective (no temperature variation)

• Check the sensor connections.

• Make sure that the sensor is clipped to the tube.

F72

Permanent temperature diff erence

between fl ow and return heating

sensors

Mismatch between the fl ow and return

heating temperatures (permanent diff erence)

• Check temperature sensors connections.

• Replace faulty sensors.

F73

Heating circuit pressure sensor fault

The sensor is shorted or disconnected.

• Check the sensor’s connections.

• Check the sensor.

F74

Heating circuit pressure sensor fault

Fault in pressure sensor

F76

Thermal fuse fault

Thermal fuse disconnected

Defective thermal fuse

• Check the fuses connections.

• Replace the heat exchanger.

F77

Fault in gas valve motor.

Defective gas valve.

Defective condensate pump (option)

• Check the gas valve connections.

• Check the operation of the gas valve.

• Check the operation of the condensate pump (option).

F83

No water in the installation : the

temperature does not increase when the

burner is lit

Return water valve closed

Pump disconnected

Leak in the installation

• Fill the installation.

• Purge the installation.

• Check the pump connections.

• Check the fl ow and return heating sensor

connections.

• Check that there are no leaks.

F84

Permanent temperature diff erence

between fl ow and return heating

sensors

Inverted or disconnected fl ow and return

heating temperature sensors

Defective temperature sensors

• Check temperature sensors connections.

• Replace faulty sensors.

F85

Flow and return heating sensors fault

Flow and return heating temperature sensor

connected to same tube

• Check temperature sensors connections.

F86

Underfl oor heating contact fault

Floor heating contact open

Sensor disconnected or defective

• Check the sensor connections.

• Check that the sensor is connected to the main

board and the shunt is removed.

Err

User interface fault

Defective user interface

• Check connection from user interface PCB to main

PCB.

• Replace user interface.

MAINTENANCE

- 30 -