Maintenance – Glow-worm Ultimate c User Manual

Page 41

Advertising
background image

0020167175_01 - 02/13 - Glow-worm

17.8.2

Dismantling the burner

b

Warning:

The burner door seal (12) must be replaced each time

the burner is dismantled.

Disconnect the spark electrode connector (6) from the igniter

unit.

Remove the gas pipe (17).

Remove the connectors from the gas valve (1) and the fan (15).

Remove the retaining screw of the silencer.

Loosen the 4 nuts (7).

Remove the burner group from the heat exchanger (11).

The studs (8) fi xed to the heat exchanger must not be

damaged. Should it be damaged, replace the heat exchanger.

The burner gate insulation should not be damaged. Replace if

damaged.

17.8.3

Cleaning the heat exchanger

Clean the coil (19) in the heat exchanger (11) with water.

17.8.4 Burner

control

The burner (13) does not require maintenance and should not

be cleaned.

Check that its surface is not damage. Replace the burner if

necessary.

Following the verifi cation or replacement of the burner,

assemble the burner group as described in the following

chapter.

17.8.5

Re-assembling the burner group

Place the burner group on the heat exchanger (11).

Progressively tighten the 4 nuts (7) in an alternate order.

Reassemble the silencer.

Connect the gas tube (17) with a new gasket to the burner

group.

Connect the spark electrode connector (6) to the igniter unit.

Connect the connector to the gas valve (1) and the fan (15).

Open the appliance gas input.

Check the watertightness of the gas connection.

17.9 Service

completion

Re-check the combustion, see chapter "Combustion check".

On completion of the service, the "Benchmark" Service Record

sould be completed.

18 Replacement of Parts

Do not use reconditioned or copy parts, only use original parts

supplied by Glow-worm.

If a part is required, contact the Glow-worm service

organisation.

Please quote the name of the appliance, this information will

be on the name badge on the front of the appliance.

If in doubt seek advice from the local gas company or Glow-

worm’s own service organisation.

a

DANGER:

Replacement of parts must be carried out by a competent

person approved at the time by the Health and Safety

Executive.

PLEASE NOTE: During change of part of the combustion circuit, we

recommend that the following is the following must be checked:

- The integrity of the fl ue system and the fl ue seals,

- The integrity of the boiler combustion circuit and the relevant

seals,

- The operational (working) gas inlet pressure at maximum rate,

- The gas rate,

- The combustion performance.

18.1 General

b

ATTENTION:

The replacement of parts described in sections

"Combustion block" will require the removal of the

burner module assembly and the replacement of seal

and self locking nuts.

Replacement parts that have associated components that need to

be replacing on removal, i.e. ‘O’ ring, seals, gasket, etc., will be

supplied and should be fi tted.

Before replacing any parts of the boiler, isolate from the mains

electric supply and turn off the gas at the gas service isolation

valve on the boiler.

Unless stated otherwise parts are replaced in the reverse order to

removal.

After replacing any parts, always test for gas tightness and if

necessary carry out functional test of the controls.

MAINTENANCE

- 39 -

Advertising