14.2 Fault

memory

This menu allows you to display the 10 most recent failure

codes registered by the appliance.

In order to display the fault code memory, simultaneously

press the buttons and for more than 7 seconds.

The screen will display the fi rst fault "1." (record) and after

"XX" (fault code).

To display the other faults registered by the appliance, press

the button or .

Press button

for more than 3 seconds to exit this menu.

To erase the fault memory registered by the appliance, consult

the “Installation adjustments” chapter and use code “d.94”.

14.3 Fault

codes

i

IMPORTANT:

The faults described in this chapter should be carried

out by a qualifi ed engineer and if needed by the After

Sales Service.

Fault

codes Description

Cause

Solution

F00

Flow heating temperature sensor fault

Sensor open circuit

• Check the sensor’s connections.

• Check the wiring harness.

• Check the sensor.

F01

Return heating temperature sensor fault Return heating temperature sensor

disconnected

F10

Flow heating temperature sensor fault

Sensor short-circuit

F11

Return heating temperature sensor fault Return heating temperature sensor shorted.

F20

Overheating fault

Overheating safety device activated (97°C)

• Check the operation of the pump.

• Check the wiring harness.

• Check that the fl ow and return heating isolation

valves are open.

F22

Water pressure of the installation (<0.3

bar)

Return water valve closed

Pump disconnected

Leak in the installation

• Fill the installation.

• Purge the installation.

• Check the pump connections.

• Check the fl ow and return heating sensor

connections.

• Check that there are no leaks.

F23

Maximum temperature diff erence

reached between return and fl ow

heating

Water circulation fault

• Check the fl ow and return heating sensor

connection.

• Check the pump speed.

F24

Water circulation fault

Malfunction of the pump (excessively rapid

temperature increase)

• Check that the fl ow and return heating isolation

valves are open.

F26

Fault in gas valve motor.

Disconnected or defective cables

• Check the gas valve connections.

• Check the operation of the gas valve.

• Check the operation of the condensate pump (option).

F27

Flame detection fault.

Abnormal fl ame detection

• Check the fl ame detection electrode.

• Check the main board.

• Check the igniter unit.

F28

Ignition fault

No return gas / Insuffi cient gas fl ow

Gas valve incorrectly adjusted

Defective fi ring electrode and fl ame control /

Defective igniter unit

• Check the return gas circuit (gas valve open).

• Check the observe the fl ame picture and check the

CO

2

setting.

• Check the igniter unit connections.

• Check the state of the electrode (corrosion).

F29

Loss of fl ame during operation

F32

Incorrect air pressure

Incorrect fan speed.

• Check the entire fl ue system.

• Check the fan’s electrical connections.

F49

EBUS voltage fault

Fault in EBUS line

Short circuit in EBUS connector

• Check that the eBus controls are fi tted and wired

correctly.

MAINTENANCE