Installation, 2 installation settings, 3 after sales service settings – Glow-worm Ultimate c User Manual

Page 27

Advertising
background image

0020167175_01 - 02/13 - Glow-worm

12.2 Installation

settings

Push in and hold the

button for more than 7 seconds to

access the confi guration menu. The screen displays "0".

Press the button 4 times. The screen displays "96". This is

the installer's password.

Press

to validate. The screen displays a fl ashing and

alternating "d." and "00".

Press or button to access the parameter to modify.

Press

button to modify the value of the parameter and

select with the or keys.

Press

button to confi rm and save the changes.

Press and hold the

button for more than 7 seconds to

exit.

Code Parameter

Unit Description

Factory setting

Modifi able

parameter

d.00 Maximum heating power

kW

Choose a value: ULTIMATE 30c > 6 to 25

and ULTIMATE 35c > 8 to 30.

25 (ULTIMATE 30c)

30 (ULTIMATE 35c)

yes

d.01 Pump over-run time - heating

min

Choose a value between 2 and 60

5

yes

d.20 Maximum temperature setting for domestic hot water

°C

The recommended maximum temperature

setting for DHW is 60°C. Choose a value

suitable for your needs.

60

yes

d.34 Speed of fan

rpm

Fan speed is displayed between 0 and 99.

Multiply the display value by 100.

-

no

d.36 Domestic hot water fl ow

l/

min. Display domestic hot water fl ow.

-

no

d.40 Heating fl ow temperature

°C

Display the heating fl ow temperature.

-

no

d.41 Heating return temperature

°C

Display the heating return temperature.

-

no

d.43 Heating curve

K

See the instructions for the external sensor

connected to the appliance.

1.2

yes

d.47 Exterior temperature

°C

Display the temperature measured by the

external sensor.

-

no

d.67 Time remaining before the end of the anti-cycle in

heating mode.

min. Display the time remaining before the end of

the anti-cycle

-

no

d.71 Maximum temperature setting for heating outlet

°C

Select a value between 50°C and 80°C.

75

yes

d.90 Detection of eBUS controller

-

0 = Not detected

1 = Detected

-

no

12.3 After Sales Service settings

Press and hold the

button for more than 7 seconds to

access the confi guration menu. The screen displays "0".

Press or button and enter the After Sales Service

password.

Press

to validate. The screen displays a fl ashing and

alternating "d." and "00".

Press or button to access the parameter to modify.

Press

button to modify the value of the parameter and

select with the or keys.

Press

button to confi rm and save the changes.

Press and hold the

button for more than 3 seconds to

exit the confi guration menu.

Code Parameter

Unit Description

Factory

setting

Modifi able

parameter

d.08 Current state of the 230V room thermostat

-

230V room thermostat :

0 = open (no heating),

1 = closed (heating mode).

-

no

d.09 Flow temperature set point from external eBus control

°C

External eBus set value.

-

no

d.10 Heating pump status

-

0 = off

1 = on

-

no

d.16 Current state of the 24V room thermostat

°C

0 = open (no heating),

1 = closed (heating mode)

-

no

d.17 Flow or Return temperature control

°C

Temperature regulation on fl ow (radiator) or return

(under-fl oor heating) temperature sensor.

0

yes

d.22 DHW demand active (tapping)

-

0 = off

1 = on

-

no

d.23 Central heating mode

-

0 = CH not available (summer mode)

1 = CH available (winter mode)

-

no

d.33 Speed setpoint of fan

rpm

Fan speed is displayed between 0 and 99.

Multiply the displayed value by 100.

-

no

INSTALLATION

- 25 -

Advertising