3 flue options and terminal clearances – Glow-worm Ultrapower sxi Range User Manual

Page 11

Advertising
background image

11

HORIZONTAL FLUES

A DIRECTLY BELOW AN OPENING, AIR BRICK,

OPENING WINDOWS

300

B

ABOVE AN OPENING, AIR BRICK,

OPENING WINDOWS

300

C

HORIZONTALLY TO AN OPENING,

AIR BRICK, OPENING WINDOWS

300

D BELOW GUTTER, DRAIN/SOIL PIPE

25

E BELOW EAVES

25

F BELOW A BALCONY OR CAR PORT

25

G FROM VERTICAL DRAIN PIPES AND

SOIL PIPES

25

H FROM INTERNAL/EXTERNAL CORNERS

25

H

*

TO A BOUNDARY ALONGSIDE THE

TERMINAL

300

I

ABOVE ADJACENT GROUND OR

BALCONY LEVEL

300

J

*

FROM SURFACE OR A BOUNDARY

FACING THE TERMINAL

600

K FACING TERMINALS

1200

L FROM OPENING (DOOR/WINDOW)

IN CAR PORT INTO DWELLING

1200

M VERTICAL FROM A TERMINAL

1500

N HORIZONTALLY FROM A TERMINAL

300

VERTICAL FLUES

P

FROM ANOTHER TERMINAL

600

Q ABOVE ROOF LEVEL

300

R

FROM ADJACENT OPENING WINDOW

1000

S

FROM ADJACENT WALL TO FLUE

300

Diagram 3.1

3.1 Flue Options

There are various flue options to choose from as illustrated in

diagram 3.3. The flue lengths and installation of various flue

types are described in section 10.

3 Flue Options and Terminal Clearances

Diagram 3.2

15583

3.2 Flue Terminal Position

The minimum acceptable siting dimensions for the terminal

from obstructions, other terminals and ventilation openings

are shown in diagram 4.2. In IE the minimum distances for

flue terminal positioning must be those detailed in I.S.813

“Domestic Gas Installations”.

The terminal must be exposed to the external air, allowing free

passage of air across it at all times.

Being a condensing boiler some pluming may occur from

the flue outlet. This should be taken into consideration when

selecting the position for the terminal.

NOTE: If necessary it is permitted to increase the terminal

protrusion through the outside wall to greater than the

minimum dimension of 87mm but no more than 600mm.

Carports or similar extensions of a roof only, or a roof and

one wall, require special consideration with respect to any

openings, doors, vents or windows under the roof. Care is

required to protect the roof if made of plastic sheeting. If

the carport comprises of a roof and two or more walls, seek

advice from the local gas supply company before installing the

boiler.

H* and J* See diagram 4.2 . These dimensions comply with

the building regulations, but they may need to be increased to

avoid wall staining and nuisance from pluming depending on

site conditions.
NOTE: If the flue terminal is positioned near a light source

insects may enter the flue system. Where safe and practical to

do so advise the homeowner to check the flue outlet and clear

visible insects from the terminal end.
Plume Management Kit: Part No.A2044100 (white) or

A2044000 (black) can be used to overcome many site issues.

3.3 Terminal Guard

A terminal guard is required if persons could come into contact

with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide

minimum of 50mm clearance from any part of the terminal and

be central over the terminal.
The guard should be similar to that shown in diagram 3.2.
A suitable guard is manufactured by: -
Tower Flue Components
Morley Rd.
Tonbridge
Kent TN9 1RA.
Size: 280mm x 165mm. Part No. CGDK3

Advertising