5 flue fitting – Glow-worm Ultrapower sxi Range User Manual

Page 26

Advertising
background image

26

Diagram 10.7

12929

Diagram 10.8

12977

Diagram 10.9

10 Telescopic Flue - Length, Preparation and Installation

13296

10.5 Flue Fitting

IMPORTANT:-

The flue seals are sensitive to mineral oil based lubricants.

Do

not grease the seals. If the seals do need to be lubricated

use only water.

During the installation of the flue system, ensure that debris

such as mortar, filings or swarf are cleared from the flue

system before completion.

Inspect the flue pipes before fitting and do not install damaged

or dented flue components.

When assembling the flue system, ensure that the inner

seals are not damaged, do not install a flue component with a

damaged seal.

When fitting flue elbows ensure that they are fitted at the

correct angle to avoid strain, this will ensure that the seal fits

correctly preventing leakage.
With the air duct seams aligned and the flue set to the

required length ‘Y’, mark the securing hole position in the air

duct. Drill a 3mm diameter hole at this position, take care not

to pierce the inner flue duct. Secure with screw provided and

tape the joint, see diagram 10.7.
Fit the sealing collar onto the locating ring on the flue terminal,

see diagram 10.8.
With the flue elbow removed, push the flue assembly into

the wall, externally or internally, until the end of the assembly

protrudes a short way from the inside face of the wall. This

will enable the internal trim ring (if required) to be positioned

and allow the flue assembly to be drawn back up to the flue

elbow.
Secure the flue elbow in position on top of the boiler with four

torque headed screws supplied.
Draw the flue assembly from wall and engage the flue duct

into the elbow and butt fit between the air duct and flue elbow.

Fit the securing collar into position.

Ensuring correct alignment of the flue, mark through two of

the pre drilled holes in the securing collar. Remove securing

collar and drill two 3mm diameter holes one in the elbow and

one in the air duct, take care not to pierce the inner flue duct.

Fit the securing collar and secure with screws provided, see

diagram 10.9.
Slide the internal trim ring back against the wall, securing in

place with a small amount of sealant if required.

Insert the flue duct into the air duct terminal assembly,

remembering to engage the catch within the terminal.
Check that the outer rubber sealing collar makes an effective

seal against the wall face.

Advertising