12 commissioning – Glow-worm Ultrapower sxi Range User Manual

Page 41

Advertising
background image

41

12 Commissioning

4. Fully open the taps on the filling loop to fill the

heating system to a pressure of 1.0bar. Close the filling

taps. If the domestic cold water is below 10

O

C the tank

frost protection may operate and a F1 will be displayed,

clear by pressing “Reset”, you may have to repeat this

process until the pressure is 1 bar.

5. Vent all air from the system and vent the CH pump via the

front screw - repeat step 4 as necessary until the system

is full and all the air has been removed.

6. Make sure that the automatic air vent works correctly and

that the black cap is loosely fitted to allow air to escape.
7. To comply with the water regulations the flexible hose

must be disconnected from the double check inlet valve

- undo the nut and pull the flexible hose from the valve.

12.4 Initial Lighting

NOTE: The combustion for this appliance has been checked,

adjusted and preset at the factory for operation on natural gas

(G20) as defined on the appliance data label.

No measurement of the combustion is necessary.

Having checked :

● the appliance has been installed in accordance with the

instructions.

● the integrity of the flue system and flue seals.

● the integrity of the appliance combustion circuit and

relevant seals.

● that all internal/external controls are calling for heat.

● the gas service isolation valve, diagram 12.1, is open.

LPG Conversion:

See section 12.11.

As an option, a chargeable boiler only commissioning service

can be provided by Glow-worm Service by calling telephone

No. 01773 828100.
Light the appliance by following the procedure below:
Refer to diagram 12.4 and repeatedly press the “MODE”

button
until the

°C

bar

and

°C

bar

symbols are displayed.

The hot water tank has priority over central heating.
The appliance will enter a self-checking routine then the

ignition sequence will commence.
The digital display will show the tank temperature setting in

hot water mode.

If the burner fails to light the fan will stop. Initially this may be

due to air in the gas supply line. The boiler will automatically

have five attempts at ignition.
If the burner fails to ignite the display will show F1.
Depress the “reset” button on the fascia to clear the display

and repeat the ignition sequence.
When the tank is full (and after a short pump overrun period)

a central heating demand will be initiated.
Once the system has been purged of air set the hot water

to the desired temperature by using the hot water “+” and “-”

buttons.
Open a hot water tap, check that hot water is available and

then close the hot water tap.
Set the central heating water temperature to the desired

temperature by using the central heating “+” and “-” buttons.

FILLING

LOOP

VALVE

FILLING

LOOP

FLEXIBLE

HOSE

DOUBLE

CHECK

INLET

VALVE

QUICK

RELEASE

NUT

QUICK

RELEASE

NUT

FILLING

TAP "B"

FILLING

TAP "A"

13371

Diagram 12.3

MODE

PROG

Ext

SYMBOLS DISPLAYED ON THE LCD AND DESCRIPTIONS

Will be displayed when domestic hot

water temperature is less than 50

o

C

System Pressure

Max burner display

Glow-worm control (Optional)

Outdoor sensor (if fitted)

Min burner display

Temperature

Appliance OFF

Central Heating

Timed Mode

Programmer

Adjustment Mode

Domestic Hot Water Function

Central Heating Function

Ext

Eco

LCD

DISPLAY

RESET

BUTTON

DHW CH

TEMPERATURE

ADJUSTMENT

TOGGLE BUTTON

MODE and PROG

Diagram 12.4

13176

The appliance will then continue to fire in central heating

mode until the user controls are satisfied or there is another

demand made for hot water.
NOTE: After ignition in central heating demand the boiler will

remain at minimum power for one minute before going to full

rate

Advertising