Glow-worm Ultrapower sxi Range User Manual

Page 29

Advertising
background image

29

10.7 Standard Horizontal Flue

Refer to diagram 10.12 for kit contents.

10.8 REAR Flue

With the flue elbow temporarily fitted, measure the distance

from the outside wall to the butt joint, see diagram

10.14.

If

the measurement ‘Y’ exceeds 667mm, then the appropriate

length of extension pipe is required. The minimum dimension

is 156mm to suit a 75mm min wall thickness. The flue can

project to a maximum of 600mm, if this is desirable, refer to

diagram 10.16.

10.9 SIDE Flue

With the flue elbow temporarily fitted, measure the distance

from the outside wall to the butt joint, see diagram

10.15.

If

the measurement ‘Y’ exceeds 667mm, then the appropriate

length of extension pipe is required. The minimum dimension

for LH is 408mm and RH 195mm to suit a minimum wall

thickness of 75mm. The flue can project to a maximum of

600mm, if this is desirable, refer to diagram 10.16.

10.10 Flue Fitting

IMPORTANT:-

The flue seals are sensitive to mineral oil based lubricants.

Do

not grease the seals. If the seals do need to be lubricated

use only water.

During the installation of the flue system, ensure that debris

such as mortar, filings or swarf are cleared from the flue

system before completion.

Long lengths of flues must be secured to the walls or ceilings

they run against. Use at least one fixing bracket for every flue

extension that is used.

After cutting inner flue tubes ensure that you de-burr and

chamfer the male tube end to prevent damage.

Inspect the flue pipes before fitting and do not install damaged

or dented flue components.

When assembling the flue system, ensure that the inner

seals are not damaged, do not install a flue component with a

damaged seal.

When fitting flue elbows ensure that they are fitted at the

correct angle to avoid strain, this will ensure that the seal fits

correctly preventing leakage.
Remove the flue elbow.
Separate the flue duct from the terminal by twisting to release

the terminal catch, then pull out of the retaining seal, refer to

diagram 10.17.
The flue duct cutting length (L + 11mm.) is shown in diagram

10.17.
The air duct should be cut at the opposite end to the terminal
The plastic flue duct MUST be cut at the opposite end to the

terminal catch.
The plastic flue duct extensions MUST be cut at the opposite

end to seal.
Insert the flue duct into the air duct terminal assembly,

remembering to engage the catch within the terminal.
Fit the sealing collar onto the locating ring on the flue terminal,

see diagram 10.8.

13224

Left Hand illustrated

10 Standard Flue - Length, Preparation and Installation

Diagram 10.14

13223

12979

Diagram 10.15

Diagram 10.16

Advertising