14 Fault Finding

Central heating mode

Description

S.00

no heating required

S.01

fan pre-run

S.02

pump pre-run

S.03

ignition

S.04

burner on

S.05

pump / fan overrun

S.06

fan overrun

S.07

pump overrun

S.08

Anti cycling period

Check flow & return thermistor connections to pipes.

Check harness connection to thermistor.

Check harness wires are not trapped between any

internal components.

Check flow & return thermistor connections to pipes.

Check harness connection to thermistor.

Check harness wires are not trapped between any

internal components.

Check flow & return thermistor connections to pipes.

Check harness connection to thermistor.

Check harness wires are not trapped between any

internal components.

Tank Loading

S.20

domestic hot water cycling mode active

S.21

fan pre-run

S.22

Pump pre run

S.23

ignition

S.24

burner on

S.25

pump / fan overrun

S.26

fan overrun

S.27

pump overrun

S.28

Anticycling period

Special cases of status messages

S.30

No Heating demand from external controls 230V Check wiring in external controller.

Check wiring at Installer Interface.

S.31

summer mode

Check CH setpoint / Check external controls

S.32

Antifreeze active – fan speed variation too high Check fan connection.

– waiting during blocking function

S.34

frost protection active (Priority 4)

Temperature below 8

O

C - check thermistor

connection if this is not true.

S.36

No Heating demand from external controls 24V Check wiring in external controller.

Check wiring at Installer Interface.

S.42

Accesory Module is blocking burner operation Check accessory module.

S.53

waiting time: temperature difference flow

- return sensor too high (Check thermistor fit)

S.54

waiting time: no water in system, temperature

(gradient error) rise flow / return sensor too high

S.76

Waiting period – pressure sensor

Check system pressure - default display.

S.96

Return-Sensor check is running, demand

Check return thermistor connection to pipe.

(DHW or heating) is blocked

Check harness connection to thermistor.

S.97

Water pressure sensor check is running,

Check connection to pressure sensor.

demand (DHW or heating) is blocked

Check pump has not seized.

S.98

Flow / Return - sensor check is running, demand

(DHW or heating) is blocked

NORMAL OPERATING

STATE FOR CH

NORMAL OPERATING

STATE FOR TANK LOADING

Diagram 14.6

13605

STATE LISTS

State list - Accessed through Diagnostic Codes - Level 1, Installer Access d.99

14.4 Status Codes

The status codes provide information about the current

operating condition of the boiler and can be accessed through

the diagnostic display, refer to diagram 14.6.