Horizontal telescopic flue – Glow-worm Ultrapower sxi Range User Manual

Page 23

Advertising
background image

23

10.1 Flue Length

The maximum achievable rear and side flue length for a

telescopic flue, diagram 10.2, is as shown in diagram 10.1.
The maximum permissible horizontal flue length is 8 metres

plus the flue terminal assembly, this can be achieved by

use of the accessories, see diagram 10.3, however should

additional 87.5

o

or 2 x 45

o

elbows be used then the length

MUST be reduced by 1metre.

13339

10 Telescopic Flue - Length, Preparation and Installation

When extension pipes are used the flue system must be

designed to have a continuous fall to the boiler of at least 2.5

o

44mm/metre to allow condensate to run back into the boiler

and out via the condense trap & siphonic drain.
The flue can be installed from inside the building, when

access to the outside wall face is not practicable.
The diagrams below describe the lengths achievable without

the use of extensions or elbows.

Horizontal Telescopic Flue

Diagram 10.1

13337

L

FLUE

C

Max flue length 668mm

181

394

5mm

min.

clearance

A

OUTSIDE

WALL FACE

87min

NOTE. If necessary, it is

permitted to increase this

dimension to 600mm max.

INTERNAL

SURFACE

Max. distance from outside

wall face to min clearance.

LH - 269mm

RH - 482mm

Min. distance from outside
wall face to min clearance.

LH - 75mm

RH - 75mm

A

320 min. to 523 max.
WALL THICKNESS

87min

NOTE. If necessary, it is

permitted to increase this

dimension to 600mm max.

455

145

OUTSIDE

WALL

FACE

INSIDE

WALL

L

FLUE

C

81