3 id-net™ interface, 1 id-net™ cables, Id-net™ interface – Datalogic Scanning Matrix 400 User Manual

Page 60: Id-net™ cables, 3 or

Advertising
background image

MATRIX 400™ REFERENCE MANUAL

50

4

4.3 ID-NET™ INTERFACE

CBX100/500 Function

Shield

Network Cable Shield

ID+

ID-NET™ network +

ID-

ID-NET™ network -

REF Network

Reference


4.3.1 ID-NET™ Cables


The following instructions are referred to Figure 57, Figure 58 and Figure 59.

The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22) stranded flexible.

We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V

Cable Shield MUST be connected to earth ground ONLY at the Master.

NEVER use ID-NET™ cable shield as common reference.

The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).

For Common Power Connections use only 2 wires (ID+ and ID-).

-

DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do

not put it together with AC cable):

-

Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8

Volts.

-

Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide

loops between them).

Reader's chassis may be connected to earth.

Network inside the same building.


Baudrate Table

Baud Rate

125 kbps

250 kbps

500 kbps

1Mbps

Cable Length

1200 m

900 m

700 m

*


* Application dependent, contact your Datalogic Automation representative for details.

NOTE

The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Datalogic Automation personnel only.


Advertising