MATRIX 400™ REFERENCE MANUAL

76

5

5.8 INPUTS


There are two optocoupled polarity insensitive inputs available on the M16 19-pin connector
of the reader: Input 1 (External Trigger) and Input 2, a generic input:

The External Trigger can be used in One Shot Mode or in Phase Mode. Its main functions
are:
 acquisition trigger in One Shot Mode
 reading phase-ON/reading phase-OFF command in Phase Mode

The main functions of the general purpose Input 2 are:
 second external trigger in Phase Mode
 match code storage command when the Match Code option is enabled

The electrical features of both inputs are:

INPUT |

V

AB

| Min.

| V

AB

| Max.

I

IN

Max

.

Open

0 V

2 V

0 mA

Closed

4.5 V

30 V

10 mA


The active state of these inputs are selected in software. Refer to the VisiSet™ Help On
Line.

An anti-disturbance filter is implemented in software on both inputs so that the minimum
pulse duration is

 0.5 milliseconds. This value can be increased through the software

parameter Debounce Filter, see the Digital I/O folder in the VisiSet™ Help On Line for further
details.

These inputs are optocoupled and can be driven by both NPN and PNP type commands.

NOTE

Polarity insensitive inputs assure full functionality even if pins A and B are
exchanged.



The connections are indicated in the following diagrams:

Pin Name

Function

A

Vdc

Power Supply input voltage +

B

I1A

External Trigger A (polarity insensitive)

C

I1B

External Trigger B (polarity insensitive)

L

GND

Power Supply input voltage -



The yellow Trigger LED (Figure 19, 5) is on when the active state of the External Trigger
corresponds to ON.