Kipp&Zonen COMBILOG Data Logger User Manual

Page 125

Advertising
background image

<ident> device identification

length = 32 byte

<length vendor name>

binary (hex 0A)

1 byte

<length controller type>

binary (hex 08)

1 byte

<length hw-release>

binary (hex 05)

1 byte

<length sw-release>

binary (hex 05)

1 byte

<vendor name>

ASCII ("Friedrichs")

10 byte

<controller type>

ASCII ("COMBILOG")

8 byte

<hw-Revision>

ASCII ("xy.yy")

5 byte

<sw-Revision>

ASCII ("xy.yy")

5 byte

x … “V“

: universal program

y.yy

: version

<Ginfo> device information

length = 27 byte

<location>

ASCII

20 byte

<serial number>

ASCII

6 byte

<number of channels>

binary

1 byte

<status> status information

length 6 byte

<channel status>

binary

4 byte

<module status>

binary

2 byte

<channel status> = K32..K25 K24..K17 K16..K9

K8..K1

Byte 1

Byte 2

Byte 3

Byte 4

<module status> = M16..M9

M8..M1

Byte 5

Byte 6

If the bit Kn in the channel status is set it indicates that an error
has occurred in channel n. A channel error is given when the
measuring value is outside of the linearisation, e.g. in case of a
sensor break down or of a short circuit of transmission.
If a bit in the module status is set it indicates that an error has
occurred in the data logger. Valid is:

Hardware Manual COMBILOG 1022

125