bit 1 = 1: EEPROM error

bit 5 = 1: (RTC-Error)

bit 2 = 1: FLASH error

bit 6 = 1: (currently not occupied)

bit 3 = 1: ADC error

bit 4 = 1: configuration error bit 16 = 1: (currently not occupied)

<Kinfo> channel information

length = 32 byte

<channel type>

binary

1 byte

<channel notation>

ASCII

20 byte

<data format>

binary

1 byte

<field length>

binary

1 byte

<decimals>

binary

1 byte

<unit>

ASCII

6 byte

<host input>

binary

1 byte

<type of calculation>

binary

1 byte

Coding <channel type>:
hex 00:

Empty Channel (EM)

hex 01:

Analogue Input Channel (AI)

hex 02:

Arithmetic Channel (AR)

hex 03:

Digital Output Channel (DO)

hex 04:

Digital Input Channel (DI)

hex 05:

Setpoint Channel (SP)

hex 06:

Alarm Channel (AL)

Coding <data format>:
hex 00:

no format

hex 01:

B O O L

hex 02:

INTEGER

hex 03:

R E A L

hex 04:

S E T 8

Hardware Manual COMBILOG 1022