Format of the status message:

=

Time ; N ; Location ;

SN ; A ; KS ; MS

=

Start-Delimiter

Time Date/Time (12 character, format YYMMDDHHmmSS)
;

delimiter

N

Module address (2 char)

Location

Module location (20 char)

SN

Serial number (6 char)

A

Alarm

condition

(2

char)

01

at

system

error

02

at

range

error

03 at threshold condition

CS

channel status (8 char, see chapter 11.8 )

MS module state (4 char, see chapter 11.8)

Example:
=000121083120;01;Testboard ;
090658;03;00000000;0000

In case of using a GSM modem it is possible to send mes-
sages as SMS (short message service). In the configuration
program the user has to define the number of the service
centre (depending on the net provider), the destination number
and the message itself. For every dial condition described
above, including the 4 possible alarm conditions, a message
can be defined separately. This message will be transmitted to-
gether with the device type (COMBILOG), the serial number
and the location of the module.

To get a list of supported GSM modems please contact your
local distributor or Theodor Friedrichs & Co. directly.