Exhaust requirements, Electrical requirements – Labconco PuriCare Procedure Stations 38100 User Manual

Page 9

Advertising
background image

Chapter 2: Prerequisites

Product Service 1-800-522-7658

4

Exhaust Requirements

If you intend to connect the Procedure Station to the optional Canopy
Connection Kit, first examine the location to ensure that it is compatible with
the cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port
should be clear of structural elements, water and utility lines, or other fixed
obstructions. There should be enough clearance to accommodate a 10-inch
diameter duct. Avoid cabinet locations that require an elbow directly above
the cabinet’s exhaust connection or an excessive number of elbows in the
exhaust system. For further information about the cabinet’s exhaust system
requirements, please refer to Chapter 3: Getting Started.

Electrical Requirements

The different Biosafety Cabinet models have the following electrical
requirements:

Model #

Requirements

3480000-3480009

115 VAC, 60 Hz, 12 Amps

3480200-3480209

115 VAC, 60 Hz, 12 Amps

3480010-3480019

100 VAC, 50/60 Hz, 12 Amps

3480210-3480219

100 VAC, 50/60 Hz, 12 Amps

3480020-3480029

230 VAC, 50/60 Hz, 6 Amps

3480220-3480229

230 VAC, 50/60 Hz, 6 Amps

3481000-3481009

115 VAC, 60 Hz, 16 Amps

3481200-3481209

115 VAC, 60 Hz, 16 Amps

3481010-3481019

100 VAC, 50/60 Hz, 12 Amps

3481210-3481219

100 VAC, 50/60/ Hz, 12 Amps

3481020-3481029

230 VAC, 50/60 Hz, 8 Amps

3481220-3481229

230 VAC, 50/60 Hz, 8 Amps

Note: A dedicated outlet with a circuit breaker rated at 20 amps should
be located as close as possible to the right rear side of the cabinet, at a
height even with, or higher than, the top of the supporting structure.

Note: On 115 VAC models, both electrical outlets are protected by a ground
fault interrupter circuit (GFIC). Labconco does not recommend plugging the
Procedure Station into a GFIC outlet.

Table 2-1

Advertising
This manual is related to the following products: