Pulsair Loop-Powered Positioner Modular Accessory System (Series I90/L90)

13

8. TROUBLESHOOTING

If the unit does not appear to be functioning properly, then
make the following basic checks.

• Check all wiring to the Positioner board, solenoid valves, and

feedback potentiometer against the wiring diagrams in
Section III.A.7. Also check for broken wires and blown fuses.

• Test the input signal current and check its connections to

the M.A.S. A minimum of 3.6 milliamps is required for the
positioner to operate.

• Check air connections against the information contained in

the Manifold Block Instructions - Section III.C.1. Test the
supply air for pressure and proper connections.

• Rerun the positioner self-calibration procedure outline in

Section III.A.4.c.

NOTE: Many times M.A.S. units are received for repair at
Flowserve and the only problem with the unit is that the
feedback potentiometer is out of calibration. It is very
important that the feedback potentiometer be properly
calibrated for correct operation of the positioner board. It is
also very important that the M.A.S. shaft not be rotated out of
the quadrant for which the feedback potentiometer has been
calibrated. Whenever a problem occurs with positioner
calibration, rerun the positioner self-calibration program
described in section III.A.4.c as a first step.

Problem

Possible Cause(s)

Solution

Unit constantly

Actuator moving

Adjust ramp time

overshoots

too fast

parameter – “tS”

setpoint

No response to

Fuse is blown

Replace fuse

input signal

(L90 only)

(#5X20MM, 63 mA,
fast-acting)

Signal source

Connect good input

connected incorrectly

source as shown on

or no signal

wiring label

As signal increases Potentiometer wires

Check wiring at

actuator suddenly

(green and purple)

terminal strip per

goes full open and reversed

chart below (refer to

will not close

Section III.A.7):
TERM # POT

8

Green

7

White/Black

6

Purple

Actuator

Ramp time parameter

Adjust parameter “tS”

responding slowly

set too high

No response from

Air pressure too low

Pressure should be

piezo valve

40 psig minimum

9. CIRCUIT BOARD REPLACEMENT

a. The following information is provided if it becomes

necessary to replace the circuit board.

b. Removing and remounting the positioner circuit board

It may be preferable to wire the new circuit board to the
terminal strip before mounting the circuit board to the
M.A.S. baseplate. This can be done with the baseplate
removed from the housing, if desired. Refer to Figure 7:

1. Turn off the power supply and disconnect the circuit

board (item 1) wires from the terminal strip.
Remove the two #4 screws (item 3) and lift out the
circuit board.

2. Locate the new positioner circuit board (item 1) to the

baseplate (item 2). The bottom edge of the circuit
board fits into a groove in the baseplate as shown.

3. Secure the circuit board with two #4 x

Z|v" self-tapping

screws (item 3) through the top two holes in the
board.

4. Make electrical connections per the wiring diagrams

shown in section III.A.7.

5. Calibrate new board per section III.A.4.

NOTE: All wiring is to be run smoothly and neatly and
away from any rotating parts, using wire ties if necessary.
Use caution to avoid pinching the wires between the base
and cover flanges.

All wiring to terminal strips shall be inserted only to mid-
point of terminal strips.

Flow Control Division

Worcester Controls

Figure 7