Worcester controls – Flowserve I90 Series User Manual

Page 21

Advertising
background image

WCAIM2053

Pulsair Loop-Powered Positioner Modular Accessory System (Series I90/L90)

21

IMPORTANT: Shielded cable must be used for each intrinsically safe
circuit and, for zener barriers, the shield must be connected to a
zener barrier ground.

3. TROUBLESHOOTING POTENTIOMETER

Problem

Possible Cause(s)

Solution

Indicates

Green and Purple

Check wiring per

backwards

wires reversed

Section III.E.2.

Reverse-acting Reverse

green

and

actuator

purple wires.

Indication not

Gears slipping

Check gear tooth

consistent

engagement of face
gear (approximately

Z|zn")

Pinion gear set

Recalibrate and

screw loose

tighten set screw.

Indication not

Potentiometer needs

Calibrate

correct

to be calibrated

potentiometer per
Section III.A.4.

M.A.S. shaft turned

Recalibrate for new

more than 90 degree

quadrant.

F.

TWO-WIRE 4 to 20 mA OUTPUT TRANSMITTER OPTION

The 4-20 mA output board has been designed for use in the
Pulsair Positioner unit as a position feedback option which will
operate as a two-wire loop-powered transmitter. The circuit can
operate on 12 or 24 Volts DC, or in intrinsically safe systems.

Provided on the board is a two-pin connector for wiring the board to
the Pulsair terminal strip and a three terminal strip for connection to
the 1000 ohm feedback “B” pot (rear) of the dual potentiometer.

NOTE: Dual potentiometer option (coded P or 5) and 4-20 mA
output transmitter option (coded 4) cannot both be ordered at the
same time. The 1000 ohm Feedback “B” pot (rear) for the 4-20
mA transmitter board connects to the terminal strip on
transmitter circuit board.

1.

ASSEMBLY (Refer to Figure 22)

a. Dual Potentiometer

1. Remove single feedback pot and bracket, if installed,

and install dual pot and bracket provided. Use
existing face gear on shaft, if installed (refer to
section III.E.1).

b. 4-20 mA Output Transmitter Board

1. The circuit board (item 11) is mounted to the Pulsair

baseplate with two #4 x

C|," self-tapping screws (item

12). The terminal strip on the board should be
oriented toward the Pulsair shaft.

2. WIRING (Refer to General Wiring Arrangement on next page.)

NOTE: All wiring is to be run smoothly and neatly and away
from any rotating parts, using wire ties, if necessary. Use
caution to avoid pinching wires between the base and cover
flanges. All wiring to terminal strip should be inserted only to
mid-point of terminal strip.

a. Wire the 4-20 1000 ohm “B” (rear) potentiometer of the

dual potentiometer to the circuit board terminal strip as
follows:

Green wire to

TB-1 terminal 1

White/Black wire to

TB-1 terminal 2

Purple wire to

TB-1 terminal 3

A two-wire connector assembly connects the signal loop
to the circuit board. Connect the red wire to Pulsair
terminal A (positive) and the black wire to Pulsair terminal
B (negative).

Flow Control Division

Worcester Controls

Figure 22

NOTE: Terminal strips, shaft and potentiometer

assembly not shown for clarity.

Advertising
This manual is related to the following products: