Pulsair Loop-Powered Positioner Modular Accessory System (Series I90/L90)

WCAIM2053

b. Loop Voltage Selection

The jumpers on the circuit board must be set up for the
applied loop driving voltage. As provided, all jumpers will
be installed. See tables below for appropriate jumpers to
be used.

NOTE: Supply voltage must be constant to assure
proper operation.

Old-Style Board Jumpers

Supply

Remove Jumpers

Keep Jumpers

24 VDC

J1 and J3

J2 and J4

12 VDC

J2 and J4

J1 and J3

Intrinsically Safe

J2 and J4

J1 and J3

New-Style Board Jumpers

Supply

Jumpers J1 and J2

24 VDC

Removed

12 VDC

Installed

Intrinsically Safe

Installed

NOTE: For Intrinsically Safe Operation, the circuit must be powered
through a CSA certified zener barrier:

Entity Parameters For I.S. Operation With Barrier

Voltage

30 Volts DC

Current

100 milliamp

Power

1 Watt

IMPORTANT: Shielded cable must be used for each intrinsically safe
circuit and, for zener barriers, the shield must be connected to a
zener barrier ground.

3. CALIBRATION

a. 4-20 mA Output

To adjust the 4-20 mA output of the circuit board connect
the appropriate loop power to the circuit. Connect the
positive lead to terminal A, and the negative to terminal B.

NOTE: The voltage supply loop for the 4-20 mA output
transmitter is independent from the 4-20 mA positioner
input signal loop — they cannot share common wires.

Although the transmitter will operate with no load,
Flowserve recommends using a load of at least 100 ohms
in the current loop.

With the actuator in the full clockwise position, adjust
trimpot TP1 (labeled 4 mA) for a reading of 4 mA on a
milliammeter connected in series with the loop. Once this
adjustment is made, position the actuator to the full
counterclockwise position. Adjust trimpot TP2 (labeled 20
mA) for a reading of 20 mA on the meter. Recheck the 4
mA end of travel and make adjustments as necessary. A
good rule of thumb to follow is that if an adjustment is
made at one end of travel, always go back to the other
end to recheck its adjustment. It should not be necessary
to check each end more than three or four times before
everything is zeroed in.