Worcester controls – Flowserve I90 Series User Manual

Page 19

Advertising
background image

WCAIM2053

Pulsair Loop-Powered Positioner Modular Accessory System (Series I90/L90)

19

2. Assemble the switches and adjustment plate to the

baseplate (item 4) as shown below, using the “loose”
#4-40 x 1" screw and the #4-40 x

C|," screw (item 5)

and #4 washer (item 6). Move the adjustment plate to
a middle position and tighten the screws.

2. CAMS

Assemble the first spring
cam, the spacer and second
spring cam. To work the
spring cam down the shaft,
squeeze the two protrusions
and turn. See Figure 20.

3. WIRING

NOTE: All wiring is to be run
smoothly and neatly and
away from any rotating
parts, using wire ties, if necessary. Use caution to avoid
pinching wires between the base and cover flanges. All wiring
to terminal strip should be inserted only to mid-point of
terminal strip.

a. The wire leads will be connected to the switches as

provided. Pay close attention to the switch labels,
schematics, wire colors, etc. when wiring the switches.
Switches are to be wired to the side terminal strip as shown
in wiring diagram below. The end terminal strip is for
connecting the potentiometer and the positioner circuitry
only. See Figures 12 and 13 for location of terminal strips.

For Intrinsically Safe (I90) version only, dividers are to be
in place between terminals D and E, F and G.

b. Route the wires neatly and use wire ties if necessary. Be

certain that the wires will not get fouled on the shaft when
it rotates.

NOTE: FOR INTRINSICALLY SAFE SYSTEMS ONLY.
All inputs/outputs (“external” wiring connections) must
be run through CSA certified zener barriers.

IMPORTANT: Shielded cable must be used for each
intrinsically safe circuit and for zener barriers, the shield
must be connected to a zener barrier ground.

4. OPERATION

a. Once the M.A.S. unit has been assembled and connected

to the actuator, the switch cams can be set per user’s
requirements. Normally switch I indicates “closed” and
switch II indicates “open”.

b. The unit should be operated to ensure that switch

actuation occurs at the end of rotation (or in whatever
position is desired by the customer) repeatably.

5. TROUBLESHOOTING

Problem

Possible Cause(s)

Solution

Switches do not

Improper cam settings

Reset cams.

indicate at proper
positions

Switch does not

Switch too far

Loosen the

actuate (never

from cam

adjustment plate

trips)

screws and rotate
switches towards
shaft until actuation
is correct — retighten
screws.

Switch does not

Switch too

Loosen the

reset (always

close to cam

adjustment plate

tripped)

screws and rotate
switches away from
shaft until actuation
is correct — retighten
screws.

No indication at

Broken, defective, or

Check wiring with

terminal strip

misplaced wire

appropriate wiring
diagram per
Section III.D.3.

Cams not aligned

Cams/spacers in

Check and

with switch arms

wrong order

reassemble cams per
Section III.D.2.

Cams not pushed

Push cams into

into place

proper locations —
align with switch
arms.

Flow Control Division

Worcester Controls

Figure 20

Switch

Com.

N.O.

I

Brn/Wht

Orange

II

Red

Blue

Advertising
This manual is related to the following products: