Worcester controls – Flowserve I90 Series User Manual

Page 8

Advertising
background image

8

Pulsair Loop-Powered Positioner Modular Accessory System (Series I90/L90)

WCAIM2053

The Pulsair Loop-Powered Positioner M.A.S. as provided
by Flowserve accepts a 4-20 mA position input control
signal and uses a 5000 ohm feedback potentiometer (“A”
pot, if dual pot is installed). The 4-20 milliamp signal
also supplies all the power that the circuit and solenoid
valves require to operate — no additional power is
required. A minimum of 3.6 milliamps is needed to keep
the circuitry operating.

b. Controls

Each version of the positioner board is calibrated and
controlled by a set of three push buttons. These buttons, in
conjunction with a system of programming menus, allow
the user to calibrate, adjust and operate all features of the
positioner. An LCD display provides feedback to the user
about the menu selections and settings. The configuration
table below lists the available functions and settings.

Flow Control Division

Worcester Controls

Display

Configuring Settings/

Default

Position

Value

Setting*

Resolution

Meaning

YFct

Lin, nLin

nLin

Position feedback function

• Linear/non-linear

init

no/oCay, Strt

no

Self-Calibration

SCUr

0 MA, 4 MA

4 MA

Setpoint current range

• 0 to 20 mA
• 4 to 20 mA

Sdir

riSE, FALL

riSE

Setpoint direction

SPrA

0.0 to 100.0

0.0

0.1 %

Setpoint split range

• Start

SPrE

0.0 to 100.0

100.0

0.1 %

Setpoint split range

• End

tS

Auto, 0 to 40

0

1 s

Setpoint ramp

SFct

Lin

Lin

Setpoint function

• Linear

1 : 25

• equal percentage 1:25

1 : 50

• equal percentage 1:50

FrEE

• freely adjustable

SL 0

0.0

0.1 %

Setpoint vertices for freely

0 %

SL 1

28.5

adjustable setpoint function

10 %

SL 2

50.0

20 %

SL 3

62.6

30 %

SL 4

71.5

40 %

Vertices Displayed only

SL 5

0.0 to 100.0

78.5

50 %

when SFct = FrEE

SL 6

84.1

60 %

SL 7

88.9

70 %

SL 8

93.1

80 %

SL 9

96.7

90 %

SL 10

100.0

100 %

dEbA

AUto, 0.1 to 10.0

AUto

0.1 %

Positioner dead band

Ydir

riSE, FALL

riSE

Direction of action of manipulated variable

YnrM

MPoS, FLoW

MPoS

Manipulated variable standardization, mechanical travel, flow

YA

0.0 to 100.0

0.0

0.1 %

Manipulated variable limit

• Start

YE

0.0 to 100.0

100.0

0.1 %

• End

YCLS

YES, no

no

0.1 %

Tight shutoff of valve

AFct

oFF

oFF

Alarms function

• not present

Mi : MA

• A1 Min, A2 Max

Mi : Mi

• A1 Min, A2 Min

MA : MA

• A1 Max, A2 Max

A1

0.0 to 100.0

10.0

0.1 %

Alarm 1 threshold

A2

0.0 to 100.0

90.0

0.1 %

Alarm 2 threshold

Fct

Fault alarm output function

.H.C.

+ H + C

PrSt

no/oCAY, Strt

no

Preset (factory setting)

* Certain default settings must be changed to work with rotary actuators. Example: “YFct” must be set to “Lin.”

See section III.A.7 (OPERATION FUNCTION SETTINGS) for more information.

Advertising
This manual is related to the following products: